3G Alarm Communicator Installation Manual

System Options

11

The Programming Sections described in this document can be viewed at the SCW9055/SCW9057 LCD. To start programming enter:

[*][8][installer  code]  [851][# # # ]

,  Where  # # #   is  the  3  digit  Section  number  referenced  in  this  section.  The  Programming  Worksheets

at the end of this document can be used to record the new values when programming changes have been made from the default values.
Programming Sections are accessed through Connect24. Installers may 

review/record

 programming Options at the panel.

NOTE: 

Ethernet/Cellular Programming Sections accessed through the panel are for 

display purposes only

. Configuration changes 

must be done using Connect24.

S

YSTEM

 O

PTIONS

[001] Ethernet IP Address

Default (000.000.000.000)

Enter the IP address of the Communicator. Ensure that the IP address is unique to your Communicator on the local network. Format is
4 fields, each field is a 3 digit decimal number. Valid range: 000-255. If an IP address is programmed in this Section, the unit will oper-
ate with Static IP (DHCP disabled). Sections [002] and [003] must also be programmed when using Static IP addresses.

NOTE: 

 Default for this Section is Dynamic Host Configuration Protocol (DHCP) enabled. When enabled, the DHCP Server will set

values for: IP Address [001], Subnet Mask [002], and Gateway [003]. Programming an IP address in this Section will disable
DHCP (Static IP).

[002] Ethernet IP Subnet Mask

Default (255.255.255.000)

Enter the Ethernet IP Subnet Mask of the Communicator. Format is 4 fields, each field is 3 digits. Valid range: 000-255.

NOTE: 

If DHCP is enabled, the DHCP Server will assign the subnet mask for this Section and the programmed value will be ignored.

[003] Ethernet Gateway IP Address

Default (000.000.000.000)

Enter the Ethernet Gateway IP address of the Communicator. The gateway IP address is required when a router is used on the local net-
work to reach the destination IP address specified in Section [001]. Format is 4 fields, each field is a 3 digit decimal number. Valid
range: 000-255.

NOTE: 

If DHCP is enabled, the DHCP Server will assign the Gateway IP address for this Section and the programmed value will be
ignored.

[004] Receiver Supervision Interval

Default (0087/135)

When receiver supervision is enabled (ON) in Section [005] Toggle Option [3], the unit sends heartbeats to Ethernet Receiver 1 or Cel-
lular Receiver 1 to test the communications path. Use this Section to set the interval time (in seconds) when heartbeats will be sent to
the receivers. Valid range 000A-FFFF seconds. If the programmed value is less than (000A/10) seconds, supervision is disabled.

Receiver Window: 

This is the supervision timeout that must be configured at the central station receiver.

Recommended Values:

 This is the recommended heartbeat interval that should be programmed into the Communicator.

• For ULC installations, the Daily test transmission must be enabled over each available communication channel Sections [125] and

[225]. When programming with Connect24, the recommended intervals will be programmed automatically when the required win-
dow is selected.

[005] System Toggle Options
[1] Ethernet Receiver 1 Supervised

Default (OFF)

(

TL2753G

 only).

ON

: Ethernet Receiver 1 will be supervised and heartbeats will be sent to Ethernet Receiver 1 based on the supervision interval pro-

grammed in Section [004].

OFF

: Ethernet Receiver 1 will not be supervised. When disabled, heartbeat 1 is sent to the Ethernet receiver once every hour, regard-

less of supervision type (heartbeat 1 or 2). The heartbeat is resent every 5 seconds until ACK. If no event or heartbeat ACK is received
after (Receiver Supervision In 75 seconds), Supervisory trouble is indicated.

NOTE: 

Ethernet Receiver 2 can not be supervised.

[2] Cellular Receiver 1 Supervised

Default (OFF)

ON

: Cellular Receiver 1 will be supervised and heartbeats will be sent to Cellular Receiver 1 based on the supervision interval pro-

grammed in Section [004]. If ACK to heartbeat is not received, it is retransmitted every 5 seconds. Failure to ACK 2 consecutive heart-
beats will reset the radio.

OFF

: Cellular Receiver 1 will not be supervised. When disabled, heartbeat is not sent to the receiver. Supervisory trouble is indicated.

NOTE: 

 Cellular Receiver 2 can not be supervised.

[3] Supervision Type

Default (OFF)

ON

: Heartbeat 1 (Commercial Supervision). This supervision type is suitable for applications where swap detection is required on the

supervisory packet.

OFF

: Heartbeat 2 (Residential Supervision). This supervision type is suitable for applications where supervision of the communication

path to the receiver is required. (no swap detection).

NOTE: 

Commercial supervision is more data intensive than residential supervision and should only be used when required to meet the 

approval for the installation.

E

THERNET

/C

ELLULAR

 P

ROGRAMMING

 O

PTIONS

Summary of Contents for 3G2075

Page 1: ...LARM COMMUNICATOR Warning This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer Installation Manual...

Page 2: ......

Page 3: ...s Sections Ethernet Cellular Programming Options 11 System Options 11 Programming Options 13 Communications Reporting Codes 16 Ethernet Receiver 1 Options 18 Ethernet Receiver 2 Options 18 Ethernet Op...

Page 4: ...response may not occur in time to protect the occupants or their belongings Motion Detectors Motion detectors can only detect motion within the designated areas as shown in their respective installati...

Page 5: ...and return to normal entry NOTE Authorized access to Connect24 3G2075 TL2753G is required to modify any Ethernet Cellular Programming Section Spe cific panel Sections must be configured for proper op...

Page 6: ...ULC INSTALLATION REQUIREMENTS For ULC Residential fire and burglary applications the 3G2075 TL2753G can be used as primary communication channel via either Cellular or Ethernet as applicable or as a b...

Page 7: ...ber Installer ID Number and an Installer Password Perform the following pre installation 1 Retrieve the installer account and password from the Aurora Technical Services ATS group 2 Call VRU number 1...

Page 8: ...des shall be observed and respected during installation INSTALLING CAT 5 CABLE TL2753G ONLY A Category 5 CAT 5 ethernet cable must be run from a source with Ethernet Internet connectivity to the Commu...

Page 9: ...g on to the next number cycling through each of the 4 numbers for a total of 5 times each If all 4 numbers fail the 5 attempts an FTC trouble is displayed on the keypad 4 Panel Sections 301 302 303 an...

Page 10: ...e location is BAD move the SCW9055 SCW9057 to various suitable locations until 3 or more bars are obtained NOTE The communicator is capable of indicating signal strength even without an active SIM but...

Page 11: ...heartbeats to Ethernet Receiver 1 or Cel lular Receiver 1 to test the communications path Use this Section to set the interval time in seconds when heartbeats will be sent to the receivers Valid rang...

Page 12: ...be sent to the programmed receivers based on the settings of the periodic test transmission reporting codes 8 Cellular Low Signal Trouble Default OFF This option masks the Low Signal trouble from the...

Page 13: ...0000 FFFF 013 DLS Outgoing Port Default 0BFA 3066 The DLS Outgoing Port is used for outgoing session to DLS IV after an SMS request has been sent to the Communicator Use this Sec tion to set the value...

Page 14: ...e Time BWST Brazil Western Standard Time PST Philippine Standard Time SLT San Luis Time PIT Pratas Islands PYT Paraguay Time PIT Parcel Island Time JFST Juan Fernandez Island Standard Time MYT Malaysi...

Page 15: ...ca Standard Time PONT Phonpei Standard Time IST Israel Standard Time MAGT Magadan Island Time 3D 3 MSK Moscow Standard Time 5F 11 5 NFT Norfolk Island Time EAT Eastern Africa Time 61 12 NZST New Zeala...

Page 16: ...ent will occur when communications with the panel have been lost for more than 60 seconds 024 Panel Absent Trouble Restore Default FF Program 00 to disable this event or FF to enable This event will o...

Page 17: ...r details on settings NOTE The time interval in minutes between periodic tests is programmed in Section 125 Ethernet and Section 225 Cellular 030 FTC Restore Default FF Program 00 to disable this even...

Page 18: ...ver To configure the device to operate using this Common Receiver Mode functionality program Ethernet Receiver 1 and Cellular Receiver 1 IP address and port number with identical values NOTE When oper...

Page 19: ...lation is located behind a firewall and must be assigned a particular port number as determined by your network administrator Valid range 0000 FFFF NOTE Do not program Ethernet Receiver 1 and Ethernet...

Page 20: ...s all 0 or F will cause a Module Configuration Trouble yellow LED 12 flashes 212 Cellular Receiver 2 DNIS Default 000000 The DNIS is used in addition to the Account Code to identify the Communicator m...

Page 21: ...f minutes See Sec tions 026 029 NOTE Minimum value is 000005 minutes Programming an interval that is less than 5 minutes will disable test transmission 226 Cellular Trouble Delay Default 00 This optio...

Page 22: ...n 008 or assigned by DHCP 990 Boot Loader Version This Section will display the current Boot Loader version of the Communicator 991 Firmware Version This Section will display the current firmware vers...

Page 23: ...ss This Section will display the unique12 digit hexadecimal number assigned as the Media Access Control MAC address of the device SYSTEM RESET DEFAULTS 999 Software Default Default 99 The Software def...

Page 24: ...cate the signal levels with digit 1 and 2 a network status with digit 3 and the trouble status with digit 4 and 5 as indicated in table above For example status code 11000F would display following sta...

Page 25: ...t 06 Ethernet Trouble Check with your ISP to confirm Internet service is active in your area Ensure your Ethernet cable is securely inserted into the RJ45 jack of the Communicator and the Hub Router S...

Page 26: ...evel dBm Signal Level Status Action Required No Signal 0 0 0 108 8 bad Check all antenna connections Confirm 3G service is active in area Relocate Panel 1 Bar 1 4 0 2 108 103 weak Relocate Panel if si...

Page 27: ...range 0000 FFFF ____ ____ ____ ____ 011 Installer Code Default CAFE Valid range 0000 FFFF ____ ____ ____ ____ 012 DLS Incoming Port Default 0BF6 3062 Valid range 0000 FFFF ____ ____ ____ ____ 013 DLS...

Page 28: ...Valid range 000000 999999 minutes ____ ____ ____ ____ ____ ____ CELLULAR RECEIVER 1 OPTIONS 201 Cellular Receiver 1 Account Code Default 0000000000 Valid range 0000000001 FFFFFFFFFE ____ ____ ____ ___...

Page 29: ...____ ____ ____ ____ ____ 989 DNS 2 IP Address ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ 991 Firmware Version ____ ____ ____ ____ ____ ____ ____ ____ 992 Ethernet IP Address ____ ___...

Page 30: ...d materials any upgrades and this EULA and provided the recipient agrees to the terms of this EULA If the SOFT WARE PRODUCT is an upgrade any transfer must also include all prior versions of the SOFTW...

Page 31: ...ed or repaired in such a manner as to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim Access cards or tags returned for replacement under warranty w...

Page 32: ...ada technical specifications were met Certification Number IC 160A 3G255SM This device complies with Industry Canada licence exempt RSS standard s Operation is subject to the following tow conditions...

Reviews: