Page | 28
Dryer Master DM510
Installation Manual
Outlet sensor installation options
Option 1 By-Pass Method
–
Details
With the bypass method, a portion of the grain leaving the dryer is bypassed from the main stream
to where it passes by the sensor and then is returned to the main flow.
The Dryer Master rotary feed bypass chute accomplishes this. The chute requires 16.5 inches, 42 cm
of vertical space. For this type of installation see
Appendix 3, Option1
. The Dryer Master chute
flows approximately 50 - 75 cubic feet, 1.4
–
2.1 cubic meters per hour.
Install the chute so that there will be a continuous flow of grain and the chute will remain full.
Ensure that the grain flowing through the chute is a good representative sample of the grain to be
tested. Place the sensor in a location where it will NOT get an excess of fines or trash as this will
Figure 9
–
Outlet Fin in chute photo
Warning:
Welding on or near the sensor while it is mounted will invalidate the warranty
Note:
The installation of the outlet sensor is critical. A poorly installed outlet sensor will reduce the
effectiveness of the DM510. Locate the sensor where it will stay full. If the sensor becomes empty,
incorrect moisture will be recorded, resulting in poor control of the drying process.