Service Manual
rev 5.0 with software Ind1V022
-
inverter heatsink
-
inverter cooling fan operation
-
environment temperature
F 51
Stop limit
Stop limit has tripped
Reset: keep controller at zero >300ms.
Ensure that fault disappears after leaving the stop
limit.
Board Fault
Reset: switch power off and restart after the lamps
of keypad are off.
Check:
F 56
Generator side
current limit
Too short deceleration time
Reset has an additional 5 s time delay.
Check:
F 57
Thermistor fault
Thermistor input in relay / thermistor board has
detected motor overtemperature. Fault appears
when thermistor input has been open over 1s.
Check:
F 60
Parameter fault
Inverter has lost parameters. Drive selection
parameter has changed to 0 / none.
Download parameters from keypad
F 61
Overspeed Fault
SSU has tripped to Overspeed (hardware
supervision). Motor speed has increased above
overspeed detection level.
Reset when 1s without pulses from pulse
sensor/encoder to SSU and controller at zero
position.
Check:
F 62
Speed Difference
Fault
SSU has tripped to Speed Difference
Reset when 1s without pulses from pulse
sensor/encoder to SSU and controller at zero
position.
F 63
Stall Supervision
Fault
SSU has tripped to Stall.
Reset when 1s without pulses from pulse
sensor/encoder to SSU and controller at zero
position.
Check:
F 64
SSU Relay Test
Fault
Relay in SSU board is damaged or SSU relay is
bypassed
Reset: switch power off and restart after the lamps
of keypad are off.
Check:
F 65
SSU Watchdog
SSU internal fault
Reset: switch power off and restart after the lamps
of display are off.
Check:
F 66
SSU Overspeed
Limit
SSU overspeed limit has been set over 140% of
maximum frequency
Check:
F 70
Multicare Fault
Other D2L has tripped to fault or brake of other D2L
has not been opened. Fault is not stored into fault
history.
Check other hoisting inverter:
F 71
Brake Control Fault
Load information from hoist control unit is out of
operation window
Check
F 55
-
Some of following board is missing:
-
A = Basic I/O board
-
B = Thermistor board
-
D = Expansion board
-
board slots A, B and D
-
drive selection
-
control mode
-
generator side current limit
-
deceleration time
-
motor cooling and loading
-
thermistor connection. If expansion board
thermistor input is not used, it should be
shorted
-
motor parameters
-
the brake operation
-
function and cabling
-
maximum frequency setting parameters
-
SSU settings
Check:
-
pulse sensor/encoder function and cabling
-
pulse sensor/encoder pulse number
-
speed difference supervision settings
-
brake operation
-
pulse sensor/encoder function and cabling
-
stall supervision settings
-
ES and RDY external connections
-
OK input operation
-
change SSU board
-
interference fault between SSU board and
control board
-
component failure (control board or SSU
board)
-
SSU status (System menu / System info /
Expander boards / C: SSU / status)
-
SSU LED’s
If the fault comes again, contact service
-
set SSU overspeed limit under 140% of
maximum frequency
-
motor type plate parameters
-
maximum frequency parameters
-
fault history
-
brake operation
-
Ain2 wiring
-
settings of load measuring device
49/58