Service Manual
rev 5.0 with software Ind1V022
5 PARAMETER DESCRIPTIONS
This manual describes parameters with software Ind1V022. Under control panel there is sticker for software
version.
Parameters are assorted to Groups. All Groups are not always listed in control panel. Groups are shown in
control panel according to password level and selected functions. This feature makes visible parameter menu
simple and only needed parameters are shown.
Letter front of the code number describes variable type
A = Application
E = Expander
R = Reference
B = Button
G =Group
S = System
C = Counter
I = Info
T = Trip Counter
D = DynACode
P = Parameter
V = Value
Label Code
Function/Description
Adjustment
range
G2.1 General Parameters
Password P2.1.1
Default
768
Service 2156, shows also group G2.3. Expert
Supply Voltage
V2.1.2
Power unit nominal voltage
F 380V – 500V
Device V2.1.3
Device
Industrial
1 =
EP
2 =
EP3
Input Set
P2.1.4
Input Set selection, see chapter “Control methods”
3 =
Multistep
Analog Input Sel
P2.1.5
Analog input selection
Not used in travelling inverter.
Not used
Multicare
Load
Multicare&Load
Slow speed freq
P2.1.6
Speed when one of slow down limit switches (S11/S21) is open
0 – 250 Hz
Multistep 2 freq
P2.1.7
2
nd
preset speed. Multistep speed setting.
0 – 250 Hz
Multistep 3 freq
P2.1.8
3
rd
preset speed. Multistep speed setting.
0 – 250 Hz
Multistep 4 freq
P2.1.9
4
th
preset speed. Multistep speed setting.
0 – 250 Hz
Accel Time 1
P2.1.10
Acceleration ramp is defined from zero to motor nominal frequency
P2.2.2. Shorter values than the factory setting must not be used.
1-300 s
Decel Time 1
P2.1.11
Deceleration ramp is defined from motor nominal frequency P2.2.2 to
zero. Shorter values than the factory setting must not be used.
1-300 s
G2.1.12 Multicare, not used in D2T
Test Voltage Min
B2.1.12.1
1.00V is given to Analog output Aout2 by this button.
Off
/ On
Test Voltage Max
B2.1.12.2
1.00V is given to Analog output Aout2 by this button.
Off
/ On
Ain 1 Value
P2.1.12.3.
Value of analog input Ain1 voltage
V
Min Value Volt
P2.1.12.4.
Ain1 value when test voltage min has been selected in the other drive.
0 – 10 V
Max Value Volt
P2.1.12.5.
Ain1 value when test voltage max has been selected in the other drive.
0 – 10 V
G2.2 Motor Parameters
Motor Nom Volt
P2.2.1
Nominal motor voltage Un from motor rating plate.
0 – 750 V
Motor Nom freq
P2.2.2
Nominal motor frequency fn from motor rating plate
0 – 250 Hz
Motor Nom Speed
P2.2.3
Nominal motor speed n from motor rating plate
0 – 6000 rpm
Motor Nom Curr
P2.2.4
Nominal motor current In from motor rating plate. In multimotor drives
nominal currents must be summarized.
Nom Flux Curr
P2.2.5
Motor nominal flux current Io, same as no-load current or magnetizing
current from motor rating plate. In multimotor drives nominal flux
currents must be summarized.
If motor nominal flux current Io, is not available, it can be measured.
See chapter u/f-curve tuning.
29/58
Drivecon Inc. reserves the right to alter or amend the above information without notice.