Service Manual
rev 5.0 with software Ind1V022
9.3.1 Fault time data record
When a fault occurs, the fault number is displayed. By pushing the menu button right here you will enter the
Fault time data record menu, indicated by T.1-T.13.
In this menu, some selected important data valid at the time of the fault are recorded. The data available are:
T.1
Counted operation days
d
T.2
Counted operation hours
hh:mm:ss
T.3
Output frequency
Hz
T.4
Motor current
A
T.5
Motor voltage
V
T.6
Motor power
%
T.7
Motor torque
%
T.8
DC voltage
V
T.9
Unit temperature
°
C
T.10
Ready
Run
0=Not Ready
1=Ready
0=Not Running
1=Run
T.11
Direction
Fault
0=Off 1=On
0=No 1=Yes
T.12
Warning
At reference
0=No 1=Yes
0=No 1=Yes
T.13
0-speed
0=Not Zero Speed
1=Zero Speed
9.3.2 Fault
Counter
V4.5.1
Fault Counter
Fault counter value.
Counter value is shown in format
Fault counter value. Fault number.
E.g. 12.01 means that there has been 12 pieces overcurrent
faults.
When counter value is blinking, then you can monitor fault
counter values by pressing up and down arrows.
xx.01
xx.02
xx.03
xx.07
xx.09
xx.10
xx.11
xx.12
xx.13
xx.14
xx.25
xx.41
xx.53
xx.56
xx.57
xx.61
xx.62
xx.63
xx.99
Overcurrent fault counter
Overvoltage fault counter
Earth fault counter
Saturation trip fault counter
Undervoltage fault counter
Input line supervision fault counter
Output phase supervision fault counter
Braking chopper supervision fault counter
Inverter undertemperature fault counter
Inverter overtemperature fault counter
Microprocessor watchdog-fault counter
IGBT temperature fault counter
Profibus communication error fault counter
Generator side current limit fault counter
Thermistor fault counter
Overspeed fault counter
Speed difference fault counter
Stall supervision fault counter
Sum counter of following faults:
F4, F5, F8, F22, F23, F24, F26, F32, F33, F34, F35, F36, F37, F38, F39, F40, F48, F50, F54, F55,