Service Manual
rev 5.0 with software Ind1V022
1 GENERAL
1.1 Technical
data
Power class
002F 003F 004F 005F 007F 011F 015F 018F 022F 030F 037F 045F 055F
Power (kVA) at 400V
4.5
5.5
7 9 13 17 22 29 33 40 50 60 75
Output current In (A)
6.5
8
10 13 18 24 32 42 48 60 75 90 110
Max. current 1min (A)
10
12
15 20 27 36 48 63 72 90 113 135 165
Overloadability
1.5 x In , 1min/10min
Max. output voltage
Equal to supply voltage
Supply
Supply voltage
380-500VAC
Allowable voltage fluctuation
+/- 10%
Nominal supply frequency
50/60Hz +/- 5%
Signal input levels
Digital controls
S1, S2, DIA3, DIA4, DIA5, DID1, DID2, DID3, DID4, DID5: 42 … 240VAC; 15mA
Encoder feedback
EA+/- and EB+/-; 0/24V; 3k
Ω
; floating differential inputs
Control features
Control method
Open loop vector control
Frequency control range
0 ... 250Hz
Frequency command
Motor potentiometer or 2-4-step controller
Limit switch functions
Slowdown and stop limit inputs for both directions
Speed control range
s
N
... 100% (s
N
= motor nominal slip)
Speed accuracy
1% of nominal speed at speed range 10 ... 100%
1/3 of motor nominal slip at speed below 10%
Extended speed range
100 ... 200%
Braking torque
150%
Protections
Stall prevention
During acceleration and constant speed
Motor overload protection
Thermistor based temperature measurement
Overload protection
Fault is detected if the current momentarily exceeds 280% of rated current
Undervoltage / blown fuse
Fault is detected if DC voltage drops below 333V
Overvoltage protection
Fault is detected if DC voltage exceeds 911V
Momentary power loss
Immediate fault stop
Inverter overtemperature
Temperature sensor on the heat sink
Mechanical brake
Circuit breaker
Braking transistor
Electronic supervision for the braking chopper and for the braking resistor
Ground fault
Provided by electronic circuitry
Overspeed / stall,
Speed difference supervision
Independent measurement using sensor bearing, pulse wheel or encoder
Ambient conditions
Ambient temperature
-10
°
C ... +55
°
C (14
°
F ... 131
°
F) for ED
≤
60%
Storage temperature
-40
°
C ... +60
°
C (-31
°
F ... 140
°
F) dry
Humidity <95%RH
(no
condensation)
Altitude
Maximum 1000m at In. Above 1000m: In reduces 1% per each 100m.
Above 3000m: consult factory.
Vibration
Operation: maximum displacement amplitude 3mm at 2-9Hz.
Maximum acceleration amplitude 0.5g (5m/s²) at 9-200Hz
Conforms to LV and EMC directives.
4/58
Drivecon Inc. reserves the right to alter or amend the above information without notice.