50
SPECIFICATIONS*
GENERAL
Sampling Frequency: 32ksps (recorded and real-time meters),
128 samples per cycle (periodic waveform snapshots)
Sag/dip, swell trigger resolution: 1-cycle
(uses IEC 61000-4-30
Class S methods)
Panel indicators: RGB LEDs for monitoring on/off, energy flow,
PQ event indication, battery charging/status, wiring status
Storage
Capacity:
8GB
UL,
CE
Voltage (3)
Range: 90 to 600VRMS CATIII
Accuracy: 90 VRMS to 600VRMS = ±0.1%, <90 VRMS = 0.5%
Connections: 4 safety banana voltage inputs – 3-phase voltage
and 1 neutral/reference
Current (4)
Input: 0.333 VRMS full scale, Connections: BNC
Accuracy: ±0.1% + probe
Frequency
Range: 50Hz = 45Hz to 55Hz, 60Hz = 55Hz to 65Hz
Accuracy: 50/60Hz: ±0.001Hz
POWER QUALITY
Sag/dip, swell trigger threshold resolution: 1-cycle
Vthd: ±5% for V
≥
10% Vnom
Ithd: ±5% for I
≥
10% Inom + probe error
ENERGY PARAMETERS
(probe dependent)
(True/Active) Energy (P): 0.1%
Reactive Energy (Q): 0.1%
Apparent Energy (S): 0.1%
Fundamental Active Energy(P): 0.2%
Fundamental
Reactive Energy(Q): 0.2%
Fundamental
Apparent Energy (S): 0.2%
Demand:
0.2%