Chapter 6. Function Table & Description
Input Range
Related Function
Factory Setting
0~600[sec]
Low Water Pressure Alarm Level - OUT
Low Water Level Detection Mode
20[sec]
Pump 57 : TUL - Low Water Level Alarm Time - OUT
· It sets maintaining time of Low Water Level to issue the low water level alarm.
If the current pressure decreases under the low pressure alarm level (Pump 56) and maintains its state for
a specified time, then display the alarm and stops the operation.
Pump 56
Pump 54
Input Range
Related Function
Factory Setting
0.00~25.00[bar]
Low Water Pressure Level Alarm Time of
Pressure Sensor - OUT
Low Water Level Detection Mode
0.30[bar]
Pump 55 : TUL - Low Water level Alarm Time-LS
· It sets maintain time of low level sensor signal to issue low level alarm.
That is, if the low level sensor signal is continued for more than trip time when low level sensor is selected
from low level trip mode(Pump 54), it is required to display alarm and stop operation as it is detected that
there is no water inside of the inlet pipe.
Functional Description
0: Low water pressure level sensor off
1~600[sec]: Time Setup [Factory Setting 2(sec)]
Pump 56 : TUL - Low Water Level Alarm - OUT
· It is a pressure level to detect low water level when the mode is software detection from Low Water Level
Detection Mode (Pump 54).
Pump 57
Pump 54
Related Function
Function Description
Low Level Pressure Sensor
Outlet Pressure
(Factory Setting)
Inlet Pressure
Pump 55
Pump 56
Pump 57
Pump 58
Pump 59
TUL-Low Water Level Alarm Time - LS
TUL-Low Water Level Alarm - OUT
TUL-Low Water Level Alarm Time - OUT
TUL-Low Water Level Alarm - IN
TUL-Low Water Level Alarm Time - IN
Pump 53 : TLP- Low Pressure Alarm Time
It sets maintaining time of low pressure alarm level to issue the low pressure alarm. That is, if the current
pressure decreases under the low pressure alarm level (Pump 52) and maintains its state for a specified time,
a low pressure alarm is displayed and operation stops.
Input Range
Related Function
Factory Setting
0~200[sec]
Pump 53
Low Pressure Alarm Time
20[sec]
Pump 54 : TUL - Low Water Level Detection Mode
ㆍ
It is a mode to set up low water level alarm detection method.
ㆍ
In case of setting up low water level sensor, it is required to attach electrode outside on the pipe to detect water
inside.
ㆍ
In case of inter-operation, low water level sensor should be linked to the lowest ID Drive.
※
If there is no water on suction part, all of drives (pumps) will stop.
ㆍ
When it is set to Software detection, it detects the alarm on the basis of low water level alarm and low water level
alarm time. That is, if the operation is continued for more than low water level alarm time (Pump 56) with pressure
under the low water level alarm pressure level (Pump 57), it is required to display alarm and stop operation as it is
detected that there is no water inside of the piping.
38