Chapter 6. Function Table & Description
Input Range
Factory Setting
0.00 ~ 25.00 [bar]
16.00 [bar]
Input Range
Factory Setting
0.00 ~ 25.00 [bar]
100 [%]
Input Range
Factory Setting
0.00 ~ 25.00 [bar]
3.00 [bar]
Pump 4 : Pressure Setting
Display Setting Pressure and Pressure Settings
Pump 5 : Current Pressure
Display the current pressure.
Pump 6 : Discharge Pressure
Display the discharge pressure only for Differential Control Mode
Pump 7 : Inlet Pressure
Display the inlet pressure only for Differential Control Mode
Pump 11 : Setup the Capacity of Sensor 1
ㆍ
Enter the maximum value that the pressure sensor can measure.
ㆍ
By entering capacity of pressure sensor attached to the drive being used, it is possible to display the currently
measured pressure.
ㆍ
Enter the rated value of the pressure sensor for normal pump operation.
Pump 12 : Gain of Sensor 1
ㆍ
Adjust Gain Value to correct error
ㆍ
Sensor Value = Average of 100 times of reading value * gain/100
Input Range
Factory Setting
-2.00 ~ 2.00 [bar]
0.00 [bar]
Pump 3 : Pressure Setting
ㆍ
his allows to correct error between Analog or Digital Pressure Meter installed in the pipe and the pressure
value displayed on the Drive
ㆍ
Current Pressure Value = Sensor Value Offset Value
Input Range
Factory Setting
0.00 ~ 25.00 [bar]
16.00 [bar]
Pump 14 : Setup the Capacity of Sensor 2
ㆍ
Enter the maximum value that the pressure sensor can measure.
ㆍ
By entering capacity of pressure sensor attached to the drive being used, it is possible to display the
currently measured pressure.
Example) In case of the capacity of using sensor is 10bar, input 10.0.
ㆍ
Enter the rated value of the pressure sensor for normal pump operation.
34