Chapter 6. Function Table & Description
47
Drive 25 : Stall Prevention Level
It refers Stall protection current level against the rated current of motor.
That is, if the rated current of the motor is 10[A] and Stall protection level is 150%, Stall protection will be
applied above 15[A].
Related Function
Input Range
100~200[%]
Drive 12
Rated Current of Motor
Factory Setting
150[%]
Drive 26 : TMOH(Motor Overheating) Mode
It sets motor overheating protection function. By comparing the real time Drive’s Current against the motor
rated current, it generates a trip as follows; 120%-60
Functional Description
OFF
ON
Drive 27 : TGF(Ground) Mode
It sets ground fault protection function. It also generates Trip and blocks the output when ground
fault is generated on the output and ground fault current is more than the setting value.
Functional Description
OFF
ON
Drive 28 : TOO(Output Open Phase Protection Mode) Mode
It generates Trip and blocks the output when one of the outputs (U/V/W) of the Drive is open.
Functional Description
OFF
ON
Drive 31 : No. of Auto Restart after Trip
·It refers to No. of automatic restarting for the drive after trip.
If the trip occurs more than specified number, it cannot restart.
·If there is no trip during a certain time, No. of trip might be deleted.
·It may not restart according to error code. Refer to Fault History Table.
Input Range
0~ 100 [Times]
Factory Setting
5 [Times]