[CHAPTER 7 CAUSE OF FAULT AND REACTION]
7-7 |
DOOCHPUMP
Er-13
(Drive Overload Operation Trip-tdOL)
Cause
ㆍ
Occurred when the load is larger than the rated drive capacity.
Reaction
ㆍ
Use drive with larger capacity suitable for the load.
Er-14
(Ground Trip-tGF)
Cause
ㆍ
Occurred when Output line of drive make short circuit with ground line.
ㆍ
Occurred when insulation of motor is defective.
Reaction
ㆍ
Check the drive output wiring.
ㆍ
Replace the motor.
Er-15
(Comm. ID Duplication-tIdE)
Cause
ㆍ
Occurred upon entering same ID duplicated when assigning ID on each drive for
Multi-drive operation.
Reaction
ㆍ
Check drive ID and be sure to not to make duplication.
Related Function
Function Name
Ref. Page
Pr-51 Communication
ID
6-10~11
Er-16
(Communication Error-tCE)
Cause
ㆍ
Occurred when CAN communication lines have defective connection.
ㆍ
Occurred when drive CAN communication IC is defective.
Reaction
ㆍ
To check connection status of CAN communication lines.
ㆍ
Replace the drive.
Er-17
(The Defects of Input-tIO)
Cause
ㆍ
Occurred when input wiring is defective.
ㆍ
Occurred when input terminal contacts are defective.
Reaction
ㆍ
Check input wiring.
ㆍ
Check status of input terminals.