[CHAPTER 5 OPERATION]
5-12 |
DOOCHPUMP
Er - 01
B. Setup and Operation Method
•
After applying power supply, check if Stop LED on FND is turned on and FND part displays
current press
P - 0.0
of piping.
If
※
is displayed, be sure to check wiring of pressure sensor.
(Connection status or defective pressure sensor)
Caution: Do not surprise even if drive is automatically operate after 10 seconds from power
※
supply. This is a normal phenomenon that power fail recovery function operates.
(Refer to power fail recovery function.)
C. Operation Parameters
- Basic Setup Parameters
Setup
Sequence
Setup Item
Parameter
Code
Functional Description
1
Run Command
Input Location Setup
dr-01
To set up Run command with FND.
2
Target Frequency
Input Method Setup
dr-02
To set up Target Frequency Input Method of
drive with own PID.
3
Pump Control
Mode Setup
Pr-02
To set up Pump Control Mode to Constant
Pressure Mode.
4
Sensor1 Capacity
Setup
Pr-03
To set up rated capacity of pressure sensor
used.
5
6
Sensor1 Pressure
Variation Correction
Pr-04
To correct variation between value of used
pressure sensor and real pressure value.
Comm. ID Setup
Pr-51
To set up CAN Comm. ID to 1~6 so that it
should not be duplicated with other drive.
7
Target Pressure
Setup
St Group
To set up target pressure of pump system.
8
9
Motor Rotation
Direction Selection
dr-20
To make rotation direction of motor same as
pump operation direction
Operation
Press key, the pump operates with
target pressure.