[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-3 |
DOOCHPUMP
Name
Range
Factory
Setting
Para.
Link
Diff.
Pressure
Use
Change
on
Operation
Ref.
Page
Pr-52
CAN Comm. Speed
1~5
1
X
O
X
6-11
Pr-53 Alteration
type
0~1
0
Pr-54
Lead pump
alternation time
0~24(hour) 12 O O O
Pr-55
Standby Pump wating
time
0~100[sec] 5
Ο
Ο
O
Pr-61
PID control Type
Setup
0~1 0
O
O
X
6-12
Pr-64
Output Ratio of
Starting AllPID
Increase
70~100[%] 100 O O
O
Pr-70
High Pressure Alarm
Level
0~Sen1 Capacity
[bar]
16.0
Ο
Χ
O
Pr-71
Low Pressure Alarm
Level
0~10.0[bar] 0.5
Ο
Χ
O
Pr-72
High Pressure Alarm
Time
0~100[sec] 5
Ο
Χ
O
Pr-73
Low Pressure Alarm
Time
0~200[sec] 20
Ο
Χ
O
Pr-74
Low Level Trip Time
of Pressure Sensor
0~250[sec] 20
Ο
Χ
O
Pr-75
Low Level Trip
Pressure Level
0~1.0[bar] 0.3
Ο
Χ
O
Pr-76
Low Level Detection
Method Selection
0~1 0
X
Χ
X
6-13
6-14
Pr-77
Low Level Trip Time
of Low Level Sensor
0~250[sec] 2
Ο
Χ
O
Pr-80 Fault
History
-
-
X
O
X
Pr-81 Fault
History
1
-
-
X
O
X
Pr-82 Fault
History
2
-
-
X
O
X
Pr-83 Fault
History
3
-
-
X
O
X
Pr-84 Fault
History
4
-
-
X
O
X
Pr-85 Fault
History
5
-
-
X
-O
X
Pr-86 Delete
Fault
History
0~1
0
X
O
O
Pr-87 Sensor
percentage
0~200
100
X
X
O
6-15
Pr-90 Initialization
Code
0~1
0
X
O
X
Pr-92 S/W
Version
-
-
X
O
X