[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
6-20 |
DOOCHPUMP
dr-37 No. of Auto Restart after Trip
ㆍ
It refers to No. of automatic operations for drive after occurrence of trip.
If the trip occurs more than specified number, it can not restart.
ㆍ
If there is no trip during certain time, No of trip might be deleted.
ㆍ
It may not be restarted according to error code. Refer to Chapter 7 Fault History Table.
Factory Setting
Input Range
0~50[times]
3[times]
dr-38 Automatic Restart Waiting Time after Trip
ㆍ
When a specified time elapsed after trip, it restarts.
Factory Setting
Input Range
0~250[sec]
10[sec]
dr-40 Drive Control Mode
ㆍ
It selects V/F control or slip compensation control.
V/F control refers to a control to make ratio of output voltage and output frequency constant,
while slip compensation control makes motor speed regular with slip compensation function.
Setup Data
Functional
Description
Related Function
0 (Factory Setting)
V/F control
dr-41
Torque boost amount
dr-10 Motor
capacity
dr-12
Rated current of motor
dr-15
Non-load current of
motor
dr-16 Rated
slip
of
motor
1
Slip Compensation
Control
dr-18
Efficiency of motor
dr-35 Motor Overheat Selection
ㆍ
It sets motor overheat protection function.
The drive calculates load current of motor by itself and determines overheat by expecting
increase of temperature.
Setup Data
Functional Description
e
s
a
e
l
e
R
)
g
n
i
t
t
e
S
y
r
o
t
c
a
F
(
0
p
u
t
e
S
1
dr-36 Ground Detection
ㆍ
It sets ground protection function.
Setup Data
Functional Description
e
s
a
e
l
e
R
)
g
n
i
t
t
e
S
y
r
o
t
c
a
F
(
0
p
u
t
e
S
1
Summary of Contents for Q-Drive NQ-0075-S
Page 1: ...User Guide Model AC Drive V F D 3 Phase input www doochpump com...
Page 2: ......
Page 8: ...SAFETY PRECAUTIONS 6 DOOCHPUMP...
Page 20: ...CHAPTER 3 EXTERNAL DIMENSION 3 6 DOOCHPUMP...
Page 27: ...CHAPTER 4 INSTALLATION 4 7 DOOCHPUMP Power Range 5 5 22kW...