[CHAPTER 6 FUNCTION TABLE & DESCRIPTION]
Setup Data
Functional Description
Single Mode
0(Factory Setting)
Related Functions
dr-02
Target Frequency Input Method
Pr-52
CAN Communication Speed
Pr-53
Lead Pump Alternation method
Pr-54
Lead Pump Alternation Time
Pr-55
Stand-by Pump Waiting Time
1~6
Multi-Drive
control
Comm. ID
No.
Pr-61
PID Type on Multi-Drive control
Pr-52 CAN Communication Speed
ㆍ
It sets up CAN communication speed. In case of long connection distance, it is better to reduce
the communication speed.
Setup Data
Functional Description
40kbps
1(Factory Setting)
50kbps
2
100kbps
3
200kbps
4
250kbps
5
Pr-54 Lead Pump Alternation Time
ㆍ
Alternative operation refers to an operation that when it reaches time specified by the user, the
drive with a lot of power consumed is to be stopped and the one with less power consumption is
to be started alternatively at the same time in order to prevent a specific drive(pump) being
operated constantly. If times is set, drives are forcedly shifted.
Setup Data
Functional Description
Release of alternation
0
1~24(hour) Alternation
time
setup.
(Factory
Setting
12[hour])
Pr-53 Alternation method
ㆍ
It determines the order of Q-Driver’s run, stop, alternation on Multi-Drive operation mode.
*
Setting is available for Ver 1.3x
*
When Pr-50 can comm. mode is 0, alternation is set 0.
Setup Data
Functional Description
In order if ID
1(Factory Setting)
0
In order of low watt-hour
6-11 |
DOOCHPUMP