Code
Alarm
Description
E-42
Communication error with
BIO
Hydraulic Kit
(not valid for BIOCLASS
iC 66).
Communication failure between boiler and the
BIO Hydraulic
Kit
.
If this alarm occurs repeatedly contact the nearest official
technical assistance service.
E-43
Ashtray full.
Warning that the ashtray is full. The boiler will continue
operate normally. To restore warning, the ashtray must be
emptied and it is necessary to set the “Emptying ashes”
parameter to 0 of the “User menu” (See “Ashtray status”).
E-44
Boiler Maintenance.
Notice for maintenance of the boiler. Contact your nearest
official technical assistance service to perform periodic
maintenance of the boiler.
E-45
BT tank temperature sensor open
circuit,
Sbt
.
BT tank temperature sensor is damaged or disconnected.
Contact your nearest official technical assistance service to
have it replaced.
E-46
BT tank temperature sensor short-
circuited,
Sbt
.
E-47
Communication error with pellets level
sensing unit.
Communication failure between boiler and the pellets sensing
system board (PCB).
If this alarm occurs repeatedly contact the nearest official
technical assistance service.
E-48
Low fuel level in the hopper.
Warning that the hopper is going to run out of pellets (fuel
reserve). The boiler will continue operate normally. Refill the
hopper with pellets up to the sensor to restore the warning
alarm.
E-49
Hopper is run out of fuel.
The hopper is completely empty of pellets. The boiler stops
running to avoid emptying the auger. To restore boiler
functioning refill the hopper with pellets up to the sensor and
press RESET button.
E-50
Fuel Suction System and pellets sensing
units connected together.
Fuel Suction System and pellets sensing units are connected
together to boiler's main board. Contact your nearest official
technical assistance service to disconnect one of the units.
E-57
Zone 1
TA
1
room temperature sensor
open circuit.
The Zone 1 room temperature device is broken or
disconnected. Please contact your nearest official Technical
Assistance Service to have it replaced.
E-58
Zone 1
TA
1
room temperature sensor
short-circuited.
E-59
Zone 2
TaM
1
room temperature sensor
open circuit.
The Zone 2 room temperature device is broken or
disconnected. Please contact your nearest official Technical
Assistance Service to have it replaced.
E-60
Zone 2
TaM
1
room temperature sensor
short-circuited.
E-61
Zone 3
TaM
2
room temperature sensor
open circuit.
The Zone 3 room temperature device is broken or
disconnected. Please contact your nearest official Technical
Assistance Service to have it replaced.
E-62
Zone 3
TaM
2
room temperature sensor
short-circuited.