background image

EN 

12

 

 

BIOCLASS iC 66 

2.6

 

Installation of a room temperature sensor or thermostat 

The 

BioClass iC 66

 boiler has a 

TA

1

 (

J6

terminal strip (see "Connection Diagrams")

,prepared for the 

connection of a device to measure the temperature conditions inside the house, which will the manage 
the remote control of the heating circuit. 

These devices will need to be suitably located within the home to be able to correctly manage the 
comfort of the house. It is advisable to install them in an area of the home that has regular use (living 
room, master bedroom, or similar), if possible avoiding rooms where heat or cold could be generated, 
such as kitchens, bathrooms, refrigerated larders, etc. In turn, they must be installed at a medium 
height and as far as possible from any source of heat or cold that could distort the temperature reading, 
such as windows, fireplaces, stoves, etc. 

Two different types of devices can be connected to the 

BioClass iC 66 boiler:

 

Room sensor 

The  room  sensor  measures  the  temperature  inside  the  home  and  transmits  it  to  the  boiler  which 
displays it on the screen. The user will be able to select the desired setpoint temperature at any time 
from  the  "User"  menu,  and  will  have  the  possibility  of  adjusting  the  desired  comfort  times  for  the 
installation from the "Heating time programming" 

(see "Configuration Menu")

. The electronic control of 

the boiler will manage the operating conditions to achieve the desired comfort and will modulate the 
boiler temperature to optimise the operation and efficiency of the heating installation. 

For the correct connection of a room sensor to the 

BioClass iC 66

 boiler, proceed as follows: 

 

Unplug the boiler from the mains. 

 

Connect  the  room  sensor,  supplied  with  the  boiler,  to  the 

TA

1

  (

J6

)  terminal  strip  (see 

"Connection  Diagrams").  The  bridge  that  connects  the  terminals  of  said  strip  must  be 
removed first. 

 

Reconnect the boiler to the mains power. 

 

The boiler comes factory configured for the connection of a "Room Sensor". If for any reason 
this  is  not  the  case,  for  its  correct  configuration,  parameter 

P.46

  must  be  set  to  1  (see 

"Technical Menu"). 

 

The electronic control allows correcting the value measured by the room temperature sensor, 
using parameter 

P.51

. To make this adjustment correctly, first of all it should be waited a 

minimum  of  10  minutes  for  the  measured  value  to  stabilize  (without  touching  the  room 
temperature sensor). 

Room thermostat 

A room thermostat connected to the boiler will activate and deactivate the heating demand depending 
on its setting. In addition, if it has a time programming (chronothermostat), the user can set the desired 
heating operating periods. 

For the correct connection of a thermostat to the 

BioClass iC 66

 boiler, proceed as follows: 

 

Unplug the boiler from the mains. 

 

Connect the room thermostat to the terminal block 

TA

1

 (

J6

) (see "Connection Diagrams"), 

having previously removed the bridge that connects the terminals of said strip. 

 

Reconnect the boiler to the mains power. 

 

Lastly, the boiler must be configured to operate with "Room Thermostat", setting parameter 

P.46

 to 0 (see "Technical Menu"). 

Summary of Contents for BioClass iC 66

Page 1: ...Bioclass iC 66 Biomass boiler EN INSTALLATION AND OPERATING INSTRUCTIONS ...

Page 2: ......

Page 3: ...e operations must only be carried out by DOMUSA TEKNIK s Authorised Technical Assistance Services Incorrect installation of these boilers could result in damage to people animals or property and the manufacturer will hold no liability in such cases DOMUSA TEKNIK informs all parties concerned that in compliance with section 1 of the first additional provision of Law 11 1997 the responsibility for d...

Page 4: ...ER TANK 28 6 OPERATION WITH A BT BUFFER TANK OPTIONAL 29 6 1 OPERATION WITH A TEMPERATURE SENSOR IN THE BT BUFFER TANK P 08 1 OR 2 29 6 2 OPERATION WITH A CONTROL THERMOSTAT IN THE BT BUFFER TANK P 08 3 OR 4 30 7 OPERATION WITH A BT DUO BUFFER TANK OPTIONAL 31 8 ICONNECT CONNECTIVITY 32 8 1 REQUIREMENTS FOR CONNECTING TO ICONNECT 32 8 2 BOILER REGISTRATION IN ICONNECT 33 8 3 DESCRIPTION OF THE ICO...

Page 5: ... 4 DHW RE CIRCULATION FUNCTION P 20 2 59 17 ADDITIONAL FUNCTIONS 60 17 1 TIME OF THE FUEL SUCTION SYSTEM CYCLE P 22 60 17 2 RESET DEFAULT VALUES P 24 60 17 3 PUMPS ANTI LOCK FUNCTION 60 17 4 ANTI FROST FUNCTION 60 17 5 BOILER PRESSURE SENSOR FUNCTION 60 17 6 CONNECTING THE LAGO FB OT REMOTE CONTROL 60 17 7 ROOM THERMOSTAT CONNECTION 61 17 8 CONNECTING THE ROOM SENSOR 61 18 MULTI FUNCTIONAL RELAY P...

Page 6: ... 8 9 11 10 12 13 1 Feed auger 2 Sensor housing 3 Automatic Air vent 4 Fan 5 Heat exchanger cleaning system 6 Water pressure sensor 7 Fuel entrance safety thermostat 8 Boiler body 9 Ash drawer 10 Air pressure sensor 11 Burner 12 Peephole 13 External ash box ...

Page 7: ...tton is used to restore functioning of the boiler after a lock out situation Also it is used to exit from any of the menus or parameters of the boiler without saving it and to return to the previous menu level 17 ON touch button This button switches on and off the boiler 18 Boiler temperature touch button This button is used to select the boiler set point temperature It is also used to disable the...

Page 8: ...ot use the boiler Contact your supplier Keep the packaging elements out of reach of children as they can be dangerous Be aware that the base of the boiler is fixed to the wooden pallet with four screws When you no longer wish to use the boiler disable the parts that could be a potential source of hazard 2 1 Location The boiler must be installed in a sufficiently ventilated site away from humidity ...

Page 9: ...e should be fitted Install all the necessary safety elements expansion vessel safety valve etc to comply with the applicable regulations for the installation If the boiler is installed at a lower height than the heating installation it is recommendable to create a siphon at the boiler outlet to prevent the installation from heating up due to natural convection when heating is not required 2 3 Inst...

Page 10: ...DIN PLUS certified wood pellet The DIN PLUS or EN Plus A1certificate assures that the fuel s humidity levels and calorific value are ideal for optimum boiler functioning If this requirement is not complied with DOMUSA TEKNIK s guarantee of the appliance will automatically be null and void The following aspects must be taken into account for the correct storage of fuel Wood pellets should be stored...

Page 11: ...ith adjustable feet for height regulation In addition the tank incorporates an adjustable leg system to adjust its height IMPORTANT Ensure the height of the elliptical holes on the sides of the boiler and on the hopper coincide for correct insertion of the feed auger To do this make the necessary adjustments for height using the adjustment feet and depth correctly positioning the hopper ...

Page 12: ... and will modulate the boiler temperature to optimise the operation and efficiency of the heating installation For the correct connection of a room sensor to the BioClass iC 66 boiler proceed as follows Unplug the boiler from the mains Connect the room sensor supplied with the boiler to the TA1 J6 terminal strip see Connection Diagrams The bridge that connects the terminals of said strip must be r...

Page 13: ...sonnel and must comply with the regulations in force For the flue to create a pressure drop the following recommendations should be taken into account It should be suitably insulated It should be independently located with a separate flue for each boiler It should be vertical avoiding any angles greater than 45º It should always have the same diameter It is recommendable for it to be circular and ...

Page 14: ... J7 and a circulation pump output Bbt terminals N 7 on the connection strip J2 dedicated exclusively to managing the heating of the buffer tank Using these control elements of the boiler you will be able to manage 4 different modes of buffer tank hydraulic installation The installation type will be selected using parameter P 08 in the Technician menu on the control panel The boiler is supplied wit...

Page 15: ...orrect electrical connection of the BT buffer tank to the BioClass iC 66 boiler Unplug the boiler from the mains power Disconnect the electrical resistance Rbt connected between terminals 18 and 19 of connection strip J7 see Connection Diagram Connect the BT tank temperature sensor supplied optionally to the sensor connection strip J7 Sbt terminals 18 and 19 see Connection Diagram Insert the tempe...

Page 16: ...tank to the BioClass iC 66 boiler Unplug the boiler from the mains power Disconnect the electrical resistance Rbt connected between terminals 18 and 19 of connection strip J7 see Connection Diagram Connect the BT tank temperature sensor supplied optionally to the sensor connection strip J7 Sbt terminals 18 and 19 see Connection Diagram Insert the temperature sensor bulb in the bulb holder sheath p...

Page 17: ...lic installation of all the system components proceed as follows to carry out the correct electrical connection of the BT buffer tank to the BioClass iC 66 boiler Unplug the boiler from the mains power Disconnect the electrical resistance Rbt connected between terminals 18 and 19 of connection strip J7 see Connection Diagram Connect the NC contact normally closed on the BT tank control thermostat ...

Page 18: ...proceed as follows to carry out the correct electrical connection of the BT buffer tank to the BioClass iC 66 boiler Unplug the boiler from the mains power Disconnect the electrical resistance Rbt connected between terminals 18 and 19 of connection strip J7 see Connection Diagram Connect the NC contact normally closed on the BT tank control thermostat on the sensor connection strip J7 Sbt terminal...

Page 19: ...ly managing the DHW production in the tank integrated in the BT DUO tank a DHW temperature sensor supplied optionally must be included in the installation The boiler is supplied with this installation option disabled To enable it the electrical resistance Rbt connected between terminals 18 and 19 of connection strip J7 see Connection Diagram must be disconnected and replaced with a temperature sen...

Page 20: ... the resistance Ra supplied as standard with the boiler Insert the DHW temperature sensor bulb into the bulb holder sheath provided in the DHW tank of the BT DUO buffer tank Connect the BT DUO tank feed pump to the component connection strip J2 Bbt terminals N and 7 see Connection Diagram Connect the boiler to the mains power To correctly configure the type of installation you must adjust paramete...

Page 21: ... alarm will appear E 19 IMPORTANT Switching on the boiler with no water inside could result in serious damage 3 3 Initial calibration of the feed auger BioClass iC 66 boiler is equipped with a feed auger to supply the fuel Follow the instructions described in Installing the hopper section to install it correctly Due to diversity of feed augers and the range of different hoppers it is needed to cal...

Page 22: ...ider relevant The installer is responsible for clearly explaining to the user the functioning of any control or regulation device forming part of the installation but not supplied with the boiler Upon delivery of the boiler the user receives the following documents The boiler installation and operation manual Combustion analysis performed during commissioning The commissioning sheet ...

Page 23: ... Icon for flame detection Flame detected C Timer icons It is displayed when the real time is inside ON programmed period It is displayed when actual time is inside OFF programmed period When any screen is displayed it relates to the display of actual time programming etc D Scale marking bar The meaning can change depending on the parameter displayed Time scale Used to indicate values or settings r...

Page 24: ...ated to the inside temperature of the home or parameters related to room sensors or remote controls It is displayed when a value or setting related to OTC operating mode is shown by the numerical digits It is displayed when the direct heating circuit nº 1 demand is activated or when a value or setting related to this circuit is shown by the numerical digits It is displayed when the mixing heating ...

Page 25: ...numerical digits It is displayed when a value or setting related to the ashtray overflowing is shown by the numerical digits Display of any value or parameter related to boiler connectivity in iConnect It is displayed when a value or setting related to DHW recirculation function is shown by the numerical digits It displays blinking when the DHW recirculation pump is switched on It is displayed whe...

Page 26: ...iler temperature set point In this operating mode only the DHW service is available if there is a DHW tank installed 5 2 Operating with a Sanit DHW tank Option BioClass iC 66 boiler could be installed together with a DHW tank Sanit within the product range offered by DOMUSA TEKNIK to obtain Domestic Hot Water service Follow the instructions described in section Installing a Sanit hot water tank to...

Page 27: ...ill be calculated using the K curve therefore by selecting the boiler temperature setpoint it will only be possible to select the activation ON or deactivation OFF of the heating service of said boiler zone It is possible to disable the heating service of the boiler Summer mode by setting to OFF the boiler temperature set point by pressing symbol for heating 18 5 4 DHW temperature set point select...

Page 28: ...ill return to standby mode after a few seconds The permitted range of set point temperature is OFF 30 80 ºC The buffer tank set point temperature can also be selected by using the touch button MENU to browse to the display option Buffer tank set point temperature When this option appears on the display touch the or symbols to select the desired temperature If you wish to totally disable the centra...

Page 29: ...er temperature exceeds 60 ºC the feed pump for the buffer tank Bbt will start up to heat the BT tank The modulating burner of the BioClass iC 66 boiler will keep the water in the buffer tank at the set temperature When the temperature of the tank reaches the selected set point temperature the burner will shut down until its temperature drops to the value set in parameter P 28 by default 5 ºC below...

Page 30: ...ating demand operation of the buffer tank feed pump Bbt will be disabled Regarding the central heating service of the boiler the circulation pump BC will be activated whenever room thermostat No 1 TA1 or the remote control LAGO FB OT if present demands heating In other words when the room temperature where the thermostat or the remote control is installed is lower than that which is set When the a...

Page 31: ... be activated whenever room thermostat No 1 TA1 or the remote control LAGO FB OT if present demands heating In other words when the room temperature where the thermostat or the remote control is installed is lower than that which is set When the atmosphere reaches the desired temperature and after a time of post circulation parameter P 15 in the Technician Menu the operation of the heating pump BC...

Page 32: ...rk amplifiers are available on the market Two methods are described below to expand the coverage of the home s Wi Fi network Wi Fi repeater Consists of a device that is very easy to install which collects the Wi Fi signal from the home s network and replicates it expanding the coverage area of the Wi Fi network To do this the repeater must be installed in an area of the home where there is Wi Fi c...

Page 33: ...ou to enter the User registration data which will be used to log in to the iConnect application You will also be asked to agree to the APP s Conditions of Use and Privacy Policy Once all the requested information has been filled in the registration will be completed Once the boiler registration process has been successfully completed you will be redirected to the Login screen where by entering the...

Page 34: ... language of the Application and the possibility of contacting DOMUSA TEKNIK Technical Support to clarify any questions 8 4 iConnect App Map The iConnect Application is very intuitive and easy to use so it is not necessary to follow an instruction manual for its use In any case DOMUSA TEKNIK provides users with a series of technical information and use tutorials on its website www domusateknik com...

Page 35: ...gramme a period of days of absence from the home during which the boiler will stay turned off The boiler will turn on automatically at the end of the set period Settings This option can be used to access the General settings of the APP the registered Boilers Heating Zones and the user Account settings It is possible to activate the OTC mode of the desired boiler and select the K curve of operation...

Page 36: ...e control can adjust the building comfort level according to the weather conditions optimising fuel consumption and heating comfort in the building The LAGO FB OT remote control takes over the control of the boiler when it is connected The different selectable temperatures boiler of the boiler must be set at the remote control It is easy to install requiring only 2 wires for communication between ...

Page 37: ...activate manual mode only with the room sensor connected Real room temperature of Zone 1 only with the room sensor connected Manual mode Scheduled mode Temperature setpoint of Zone 2 adjustable using the touch selector 18 Pressing it whilst in programmed mode will deactivate said mode and activate manual mode Only with the Bio Hydraulic Kit and room sensor connected Temperatura de ambiente real de...

Page 38: ...e DHW tank option only or Boiler or buffer tank set point temperature selected using the corresponding touch button 18 only with buffer tank connected and with control by temperature sensor Actual temperature of the Buffer Tank only with buffer tank connected and with control by temperature sensor Actual boiler temperature Actual boiler water pressure Actual active boiler temperature set point ...

Page 39: ... for BIOCLASS iC 66 Actual outdoor temperature Only with Bio Hydraulic Kit option not available for BIOCLASS iC 66 Heating circuits demand 10 1 Ashtray status When Ashtray Empty Warning function is activated see Setup menu the boiler warns about the ashtray is full and must be emptied The parameter Ashtray status allows checking the fill level and the screen shows the ash scale bar which indicates...

Page 40: ... and the display will return to Setup menu Press RESET any time to go back without recording any value In the following table are listed all the parameters of Setup menu Nº Parameter Display 1 Time programming of Zone 1 Only with the room sensor connected 2 Time programming of Zone 2 Only with the Bio Hydraulic Kit and room sensor connected 3 Time programming of Zone 3 Only with the Bio Hydraulic ...

Page 41: ...timer will operate 24 hours The programming process is the same for any timer In turn each of the heating zones that may have been installed in the boiler up to a maximum of 3 zones can have their own time programming if they have a room sensor connected By default the boiler comes with the heating time schedule disabled the digits are displayed on the programming screen that is the user will manu...

Page 42: ...ected function Select the time periods 30 minutes periods by pressing o of heating 18 When the period desired is selected change it state by pressing o of DHW 19 The function will be switched off if symbol is displayed and it will be switched on if symbol is displayed After setting all the periods desired press to save and return to Setup menu level ...

Page 43: ...celled and it will be switched on permanently 11 4 Programming the Fuel suction system This programme displays the status of the pellet suction system This process is used to adjust the periods during which the operation of the pellet suction system will be enabled or disabled To disable the timer select the Fuel suction system timer programming and set it to by pressing of the boiler temperature ...

Page 44: ...activated the boiler lets us know when the boiler ash box is full so that we proceed with its emptying The parameter Ashtray status of User Menu allows checking the actual fill level When it is full an Empty the ashtray warning is activated By default the ash box reminder function is supplied activated and is set to indicative fuel consumption values which depending on the quality and type of fuel...

Page 45: ...ort management parameters from anywhere in the world see iConnect connectivity Once you have selected the iCon screen from the Configuration Menu press the symbol to access it SET will flash and use the or DHW symbols 19 to set the desired value To activate the registration of the boiler in iConnect set the value to ON Once you have completed the registration process in the APP the value REG will ...

Page 46: ...he symbols or of heating 18 When the desired parameter is displayed press to access and set it When the parameter or process has been set press again the value will be saved and the display will return to Calibration menu Press RESET any time to go back without recording any value In the following table are listed all the parameters and processes included in Calibration menu Nº Parameter Display 1...

Page 47: ... will be activated filling procedure The feed auger will be activated and a count up to 15 minutes maximum will be displayed During the process by pressing the feed auger could be stopped at any time and by pressing RESET the filling procedure could be finished and return to Calibration Menu at any time To ensure a complete filling of boiler feed auger it is recommended to make a complete 15 minut...

Page 48: ...er calibration parameter is displayed on Calibration Menu press to access SET symbol blinks and pressing again it will be activated calibration procedure The feed auger will be activated and a countdown from 200 doses will begin When the countdown finishes current calibration value will be displayed press to adjust the new value obtained during the procedure by pressing or symbols of DHW 19 Finall...

Page 49: ...n Calibration Menu press to access SET symbol blinks and pressing again it will be activated the cleaning system A countdown of 20 cycles will be displayed When the countdown is finished the cleaning device will stop By pressing the cleaning procedure can be stopped at any time and by pressing RESET it will return to Calibration Menu level 12 5 Manual circulation pumps activation By means of this ...

Page 50: ... the first parameter of Technical menu will be displayed Browse through the menu P 01 P 53 by pressing the symbols or of heating 18 When the desired parameter is displayed press to access and set it by pressing the symbols or of DHW 19 When the parameter has been set press again the value will be saved and the display will return to Technical menu Press RESET any time to go back without recording ...

Page 51: ...LASS iC 66 P 11 Heating circuit n 1 K factor curve Only with Bio Hydraulic Kit option not available for BIOCLASS iC 66 P 12 Heating circuit n 2 K factor curve Only with Bio Hydraulic Kit option not available for BIOCLASS iC 66 P 13 Boiler minimum temperature mode P 14 Minimum boiler temperature ºC P 15 Heating pump post circulation time min P 16 DHW pump post circulation time min DHW tank option o...

Page 52: ... 20 3 option only P 22 Fuel suction system cycle time s P 23 BIO Hydraulic Kit direct pump operating mode Only with Bio Hydraulic Kit option not available for BIOCLASS iC 66 P 24 Reset default values P 25 Set access code P 26 Auxiliary parameter for fuel selection P 27 Maximum heating flow temperature of mixed circuits Only with Bio Hydraulic Kit option not available for BIOCLASS iC 66 ...

Page 53: ...circuit 1 Only with Bio Hydraulic Kit option not available for BIOCLASS iC 66 P 48 Type of room temperature device in Zone 3 Mixed circuit 2 Only with Bio Hydraulic Kit option not available for BIOCLASS iC 66 P 49 Room temperature hysteresis Only with connected room sensor P 50 Minimum temperature for BT tank heating Only with buffer tank installed P 51 Zone 1 room temperature correction P 52 Zone...

Page 54: ... to set a new one P 25 press to access SET symbol blinks and it would be possible to enter the code or set it Press the o for heating symbols 18 to browse trough the digits and press the o for DHW symbols 19 to set each digit By default the access code is 1234 The P 25 parameter allows to set a new access code ...

Page 55: ...General fan speed factor P 04 Using parameter P 04 a multiplication factor for the fan speed percentage can be set when automatic fan adjustment is not activated Using this parameter the amount of combustion air can be increased or decreased to ensure correct combustion values Changing its value modifies the percentage of the fan throughout its modulation curve The selectable range of parameter P ...

Page 56: ...top the BT buffer tank heating operation The parameter P 28 can be adjusted between 5 and 40 ºC and by default it is set to 5 ºC In turn by means of parameter P 50 it is possible to set a minimum temperature at which the operation of the heating circuits connected to the buffer tank will be enabled below this temperature the heating circuits will remain deactivated The selectable range of paramete...

Page 57: ...ing operating modes can be selected P 18 0 Standard mode The circulation pump will be run depending if the heating demand is activated or not P 18 1 Continuous mode The pump continues to run provided that the heating mode is enabled boiler temperature set point different to OFF If there is room thermostat or remote control connected to the boiler the electronic controller will regulate the burner ...

Page 58: ...The optimal value will depend on the level of the home s thermal insulation the higher the insulation level the lower the value of parameter P 49 can be In turn if the insulation level is reduced it is recommended to increase the parameter This parameter will only be applied in heating zones where there is a connected room sensor The selectable range of parameter P 49 is 0 2 5ºC and the factory de...

Page 59: ...n by default 16 2 DHW pump post circulation time P 16 This function keeps the DHW valve or pump running for a period of time after deactivating de DHW service to avoid the overheating of the boiler due to the temperature inertias of the DHW installation By means of parameter P 16 the period of time that the pump valve continues to operate may be set The range of values selectable is 0 20 minutes b...

Page 60: ...dby while the boiler is plugged into the mains 17 5 Boiler pressure sensor function This function prevents boiler failure caused by a low or high water pressure level in the boiler The pressure is detected by a pressure sensor and its value appears on the control panel display in the User Menu When the pressure drops below the pressure set at P 19 parameter by default 0 5 bar the electronic contro...

Page 61: ... a J6 terminal strip prepared for the connection of a room sensor TA1 see Connection Diagrams which will make it possible to manage the heating service of the direct boiler circuit BC depending on the inside temperature of the house For correct connection and configuration carefully read the instructions in the Installing a room sensor or thermostat section The installation of a room sensor will o...

Page 62: ...s No 4 NO and N of the terminal strip J3 see Connections diagram The hydraulic installation and electrical connection of re circulation system must be made by qualified personnel During the operating periods programmed in the boiler the multi functional relay output will be activated supplying voltage 230 V between terminals No 4 NO and N of the terminal strip J3 where the recirculation pump must ...

Page 63: ...d occur repeatedly switch off the boiler and put in contact with the nearest official Technical Assistance Service 19 1 Temperature safety lock When this lock out occurs E 11 alarm code temperature alarm will appear on the screen The burner will switch off and stop heating the installation This lock out occurs when the temperature of boiler s water exceeds 110 ºC To unlock it wait until the temper...

Page 64: ...5 bar preventing it from working when the installation is drained of water either due to a leak or due to maintenance operations To unlock this alarm fill the installation again see Filling the installation up to 1 or 1 5 bar displayed on Water pressure parameter of User menu 20 SHUTTING DOWN THE BOILER Press during 1 second to shut down the boiler When the boiler is shut down the heating and DHW ...

Page 65: ...yearly 7 Clean the burner yearly 8 Check the expansion vessel It must be full according to its data plate yearly 9 Check the seal between the burner and the boiler yearly 10 Check if the hydraulic circuits are correctly sealed yearly 11 Check the water pressure of the boiler When the installation is cold it should be between 1 and 1 5 bar yearly 12 Checking the suction turbine motor brushes yearly...

Page 66: ... in order to avoid excessive ash formation A regular check of the amount of fuel should be carried out in the hopper as a lack of fuel can generate an error code E06 Dust can also accumulate at the bottom of the hopper depending on the quality and humidity of the wood pellets If there is a large quantity of wood pellet dust in the hopper DOMUSA TEKNIK s authorised technical assistance service must...

Page 67: ...67 BIOCLASS iC 66 22 3 Heat exchanger cleaning procedure The following procedure is recommended for correctly cleaning the heat exchanger 1 2 6 7 8 5 9 3 4 1h ...

Page 68: ...serious or even fatal failures for the appliance Therefore it is strictly forbidden for the user of the boiler to enter the TECHNICAL parameters which are values that can directly affect the correct operation and destruction of the appliance Only an authorized DOMUSA TEKNIK technical service can access it The user must ensure that the water pressure in the installation is correct that is a pressur...

Page 69: ...RAMS AND MEASUREMENTS 1765 670 1470 240 1360 260 520 240 755 O 175 95 130 110 110 115 115 1065 1110 1195 300 1130 IC RC VS SH V IC Heating flow 1 RC Heating return 1 SH Fume outlet V Drainage cock VS Pressure relief valve 1 2 F ...

Page 70: ...e NO Multi functional relay NC Multi function relay TA1 Room thermostat Sc Boiler temperature sensor Ra Sa DHW tank option resistance Rbt Sbt Resistance for BT tank Option RT Remote relay Sv Fan speed sensor J1 Power supply connector J2 Component connector J3 Component connector J4 Communication connector J5 LAGO FB OT remote control connector J6 Room thermostat connector J7 Sensors connector J12 ...

Page 71: ...66 24 2 Burner Qout Burner outputs connector R Ignition heater LC Burner ash cleaning device FC1 Closed switch FC2 Open switch Qin Burner inputs connector FCq Burner switch FR Photocell FCP Ash cleaning device switch ...

Page 72: ...ostat Cv Fan capacitor SPW Water pressure sensor SPA Air pressure sensor Qout Burner outputs connector Qin Burner inputs connector LCD Display communication connector J4 Communication connector S1 S2 Boiler model DIP switch J1 Power supply connector J12 Fuel suction system power supply connector ...

Page 73: ...t 10 O2 mg m3 12 CO at minimum heat output 10 O2 mg m3 34 OGC organic gaseous substances at minimum heat output 10 O2 mg m3 1 Boiler class according to EN 303 5 Clase 5 Maximum operating pressure bar 3 Maximum operating temperature ºC 80 Maximum safety temperature ºC 110 Water volume litros 154 Minimum flue draught mbar 0 10 Maximum flue draught mbar 0 20 Electrical supply 230 V 50 Hz 2 50 A Boile...

Page 74: ...r No Combustible Wood pellet Ø6 8 mm Maximum length 35 mm Seasonal yield Ƞs 84 Seasonal heating emissions Part mg m3 19 COG mg m3 1 CO mg m3 42 NOx mg m3 150 Electricity consumption at nominal power elmax kW 0 107 Electricity consumption at 30 nominal power elmin kW 0 035 Electricity consumption in standby mode PSB kW 0 004 Energy Efficiency Index EEI 123 It is recommended to use the boiler with a...

Page 75: ...al technical assistance service E 06 Ignition failure Check the fuel content in the hopper or calibrate the feed auger If this alarm occurs repeatedly contact the nearest official technical assistance service E 07 Burner ash cleaning system start step error These alarms occur when a bad running of the burner ash cleaning system is detected If this alarm occurs repeatedly contact the nearest offici...

Page 76: ...he pressure drops below 2 5 bar again Drain the installation up to 1 1 5 bar Contact your nearest official technical assistance service to have it replaced E 21 Air pressure sensor fault The air pressure sensor is damaged or disconnected Contact your nearest official technical assistance service to have it replaced E 22 Excessive air depression in the combustion chamber The air depression measured...

Page 77: ...n circuit Sr2 Underfloor temperature sensor is damaged or disconnected Contact your nearest official technical assistance service to have it replaced E 33 Underfloor temperature sensor short circuited Sr2 E 34 Outdoor temperature sensor open circuit Sext Outdoor temperature sensor is damaged or disconnected Contact your nearest official technical assistance service to have it replaced E 35 Outdoor...

Page 78: ...to run out of pellets fuel reserve The boiler will continue operate normally Refill the hopper with pellets up to the sensor to restore the warning alarm E 49 Hopper is run out of fuel The hopper is completely empty of pellets The boiler stops running to avoid emptying the auger To restore boiler functioning refill the hopper with pellets up to the sensor and press RESET button E 50 Fuel Suction S...

Page 79: ... Technical Assistance Service E 64 Communication error with iConnect module Communication error between the boiler and the iConnect electronic card If this alarm occurs repeatedly please contact the nearest official Technical Assistance Service E 65 There is no serial number on the iConnect module The serial number of the boiler has not been registered on the iConnect electronic card Please contac...

Page 80: ... any kind to its product characteristics without prior notice www domusateknik com MAILING ADDRESS HEADQUARTERS FACTORY Apartado 95 Bº San Esteban s n 20730 AZPEITIA 20737 ERREZIL Gipuzkoa Telf 34 943 813 899 Fax 34 943 815 666 CDOC002101 CDOC002101 15 10 21 ...

Reviews: