43
BIOCLASS iC 150
13
CONFIGURING THE BOILER
The following parameters in the
"Technical Menu"
allow us to set the operation of the boiler for each
installation, provided that this is done by a person with sufficient knowledge of the meaning of each setting
or by appropriately qualified staff.
13.1
Boiler Model (P.01)
Parameter
P.01
displays the model of boiler selected with the switches located on the electronic card
on the control panel:
P.01
= 150 =>
BIOCLASS iC 150
13.2
Set the boiler power (P.02, P.03)
The
BIOCLASS iC 150
boiler is configured to modulate its power between a minimum and maximum
power. Parameters
P.02
and
P.03
may be used to set the minimum and maximum burner power.
13.3
General fan factor (P.04)
Parameter
P.04
may be used to set a multiplication factor of the percentage of fan speed when
automatic fan adjustment is switched off. This parameter can be used to increase or decrease the
amount of combustion air to ensure the correct values for combustion. Changing its value adjusts the
fan percentage for the entire modulation curve. The selectable range of parameter
P.04
is 0 - 200
(default value 100), if a value under 100 is set the air quantity will reduce and if a value higher than
100 is set it will increase.
13.4
Fuel for ignition (P.05)
Parameter
P.05
may be used to adjust the amount of fuel used in the burner ignition process. The
selectable range of the parameter
P.05
is 10 - 2000 grammes.
13.5
Fuel (P.06)
Parameter
P.06
can be used to set the amount of fuel, in kilograms, that the boiler uses at 100%
power in one hour, when the combustion setting by lambda probe is switched off. This parameter is
related to the type of fuel selected, as well as the calorific value of the same. The selectable range of
the parameter
P.06
is 15.0 - 34.0 kg.
13.6
Auxiliary parameter for cleaning interval setting of the burner (P.26)
Parameter
P.26
can be used to set the combustion to the particular characteristics of each fuel. The
selectable range of parameter
P.26
is 00.0 - 99.9 kg and the default factory value will depend on the
boiler model and the type of fuel.
Summary of Contents for BIOCLASS iC 150
Page 1: ...BIOCLASS iC 150 Biomass boiler EN INSTALLATION AND OPERATING INSTRUCTIONS ...
Page 2: ......
Page 15: ...15 BIOCLASS iC 150 ...
Page 64: ...EN 64 BIOCLASS iC 150 23 CONNECTIONS DIAGRAM 23 1 Boiler ...
Page 68: ...EN 68 BIOCLASS iC 150 ...
Page 77: ...77 BIOCLASS iC 150 NOTES ...
Page 78: ...EN 78 BIOCLASS iC 150 NOTES ...
Page 79: ...79 BIOCLASS iC 150 NOTES ...