EN
70
BIOCLASS iC 150
MODEL
BIOCLASS iC 150
Rated heat output (P
ח
)
kW
145
Performance at maximum power
% (PCI)
92.1
Minimum output power (P
p
)
kW
43.4
Performance at minimum power
% (PCI)
94.1
CO at maximum power (10% O
2
))
mg/m
3
132
OGC (organic gaseous substances) at maximum
power (10% O
2
))
mg/m
3
1
Particle content at maximum power (10% O
2
))
mg/m
3
20
Particle content at minimum power (10% O
2
))
mg/m
3
16
CO at minimum power (10% O
2
))
mg/m
3
126
OGC (organic gaseous substances) at minimum
power (10% O
2
))
mg/m
3
0
Classification (as per EN 303-5)
-
Class 5
Maximum operating pressure
bar
3
Max. operating temperature
°C
80
Maximum safety temperature
°C
100
Water content
litres
202
Minimum flue draught
mbar
0.10
Maximum flue draught
mbar
0,20
Electrical supply
-
230 V~, 50 Hz, 10 A
Fume outlet diameter
mm
200
Mass flow rate of fumes at rated/minimum power
Kg/s
0.089/0.05
Fume temperature at rated/minimum power
°C
140/90
Maximum water content in the fuel
%
7
Minimum return temperature
°C
45ºC
Pressure drop on water side
(dT = 20 K)
mbar
26
Weight (net)
kg
607
Summary of Contents for BIOCLASS iC 150
Page 1: ...BIOCLASS iC 150 Biomass boiler EN INSTALLATION AND OPERATING INSTRUCTIONS ...
Page 2: ......
Page 15: ...15 BIOCLASS iC 150 ...
Page 64: ...EN 64 BIOCLASS iC 150 23 CONNECTIONS DIAGRAM 23 1 Boiler ...
Page 68: ...EN 68 BIOCLASS iC 150 ...
Page 77: ...77 BIOCLASS iC 150 NOTES ...
Page 78: ...EN 78 BIOCLASS iC 150 NOTES ...
Page 79: ...79 BIOCLASS iC 150 NOTES ...