37
BIOCLASS iC 150
11.2
Calibration of the feeder
Calibrating the boiler feed auger, the electronic control adjusts the optimum amount of fuel required
to supply the burner and produce the correct power and combustion.
If the reserve tank is empty
or runs out of fuel, it is essential to drain the boiler feed auger before carrying out the
calibration.
This display is used to calibrate the fuel feed auger required for correct boiler functioning.
It is essential that the boiler feeder is calibrated during start up
.
On selecting the "Calibration of the fuel feeder" display (
) from the
"Calibration Menu"
by pressing the symbol
we can access it and
SET
will begin flashing. Pressing symbol
again will start the
calibration process, activating the countdown from 200 doses in the
fuel feeder. When the countdown finishes the current calibration value
will be displayed and its value may be adjusted using the "
+
" or "
-
" of
DHW
(21)
. Pressing symbol
again saves the new value.
This process must be carried out at least twice to ensure that the correct amount of fuel has been
added. The steps for correctly calibrating the feed auger are as follows:
IMPORTANT: It is essential that the boiler feeder is calibrated during start up.
Summary of Contents for BIOCLASS iC 150
Page 1: ...BIOCLASS iC 150 Biomass boiler EN INSTALLATION AND OPERATING INSTRUCTIONS ...
Page 2: ......
Page 15: ...15 BIOCLASS iC 150 ...
Page 64: ...EN 64 BIOCLASS iC 150 23 CONNECTIONS DIAGRAM 23 1 Boiler ...
Page 68: ...EN 68 BIOCLASS iC 150 ...
Page 77: ...77 BIOCLASS iC 150 NOTES ...
Page 78: ...EN 78 BIOCLASS iC 150 NOTES ...
Page 79: ...79 BIOCLASS iC 150 NOTES ...