CT100G Series Inverter
CHAPTER 1 PRODUCT INFORMATION
- 8 -
Digital output
Standard 2-channel multi-function collector
outputs, one of which can be high-speed pulse
output (HDO).
Relay output
Standard 2-channel relay outputs
Communication
interface
RS485
Communication
RS485 communication interface for external
communication, support Modbus protocol
(RTU mode).
Fault protection
ACC overcurrent, DEC overcurrent, constant speed overcurrent,
ACC overvoltage, DEC overvoltage, constant speed overvoltage,
bus under voltage, motor overload, inverter overload, input
power failure, output phase loss, rectifier module overheating,
inverter module overheating, external fault, communication fault,
current detection fault, EEPROM operation fault, PID feedback
fault, factory setting time arrive etc.
Keypad display LED display
Highlight LED digital tube displays the inverter
information
Others
Running
environment
Indoors, less than 1km above sea level,
without dust, corrosive gases or direct sunlight
Ambient
temperature
-10
~
+40
℃
, derate 1% for every additional 1
℃
when the ambient temperature is between
40
~
50
℃
Humidity
5
~
95% (no condensation)
Altitude
0
~
2000m, derate 1% for every additional
100m when the sea level is above 1000m
Vibration
Less than 0.5g
Storage
temperature
−40
~
+70
℃
Control
terminals
Digital input
Standard 8-channel inputs, one of which can
be high-speed pulse input (HDI)
1.3 Product outline and installation size, weight