CT100G Series Inverter
CHAPTER 4 FUNCTION PARAMETER TABLE
- 47 -
Functio
n code
Name
Detailed instruction of parameters
Default
value
Attrib
ution
2:continue running
Ten place: user define fault 2
(
E.uD2
)
0:free stop
1:stop as stop mode
2:continue running
ten place:power on time arrive
(
E.PTo
)
0:free stop
1:stop as stop mode
2:continue running
Thousand place:reserved
0:free stop
1:DEC stop
2: DEC to 7% of motor rated frequency and
run. Automatic back to set frequency if not
loss load
Ten thousand place: PID feedback
disconnect fault
(
E.PIdE
)
0:free stop
1:stop as stop mode
2:continue running
F08.49
Fault protection act selection 4
Unit place:too big speed bias
(
E.dEU
)
0:free stop
1:stop as stop mode
2:continue running
ten place:reserved
hundred place:reserved
000
○
F08.50
reserved
F08.51
Continue running (while fault)
frequency selection
0:running as current frequency
1:running as set frequency
2:running as upper limit frequency
3:running as lower limit
4:running as abnormal standby frequency
0
○
F08.52
Abnormal standby frequency
setting
0.0%
~
100.0% (current aim frequency)
100
○
F08.53
Motor temperature sensor
types
0:no temperature sensor
1:PT100
2:PT1000
0
○
F08.54
Motor over heat protection
value
0
℃~
200
℃
110
○
F08.55
Motor over heat pre alarm
value
0
℃~
200
℃
90
○
F08.56
Instant stop not stop act
selection
0:invalid
1:DEC
2:DEC to stop
1
☆
F08.57
Judging voltage for suspended
stop instant stop act
80.0%
~
100.0%
85.0
☆
F08.58
Judging time for instant stop
not stop voltage rise
0.0s
~
100.0s
0.5
☆
F08.59
Judging voltage for instant stop
not stop act
60.0%
~
100.0% (standard bus voltage)
80.0
○
F08.60
Loss load protection selection 0:invalid
1:valid
0
○
F08.61
Detection lever for loss load
0.0
~
100.0%
10.0
○
F08.62
Detection time for loss load
0.0
~
60.0s
1.0
○
F08.63
reserved
0
~
65536
0
●