CT100G Series Inverter
CHAPTER 4 FUNCTION PARAMETER TABLE
- 60 -
Functio
n code
Name
Detailed instruction of parameters
Default
value
Attrib
ution
1: slave machine follow main machine
run command to run
Ten place: slave machine fault
information transmit
0: slave machine fault information not
transmit
1: slave machine fault information
transmit
Hundred place: main machine display
slave machine off line
0: slave machine off line main machine
not alarm fault
1: slave machine off line main machine
alarm fault (Err16)
A08.03
Main machine send data
function selection
0: run frequency 1: aim frequency
0
☆
A08.04 Receive data 0 bias
-100.00%~100.00%
0.00
○
A08.05 Receive data gain
-10.00~10.00
1.00
○
A08.06
point-to-point communication
disconnection detection time
0.0~10.0s
1.0
☆
A08.07
point-to-point communication
main machine data send
cycle
0.001~10.000
0.001
☆
A08.08
Frequency receive data 0
bias
-100.00%~100.00%
0.00
○
A08.09
Frequency receive data
gain
-10.00~10.00
1.00
○
A08.10
Slave machine frequency
FWD max bias
0.00~100.00%
10.00
○
A08.11 Window
0.20Hz~10.00Hz
0.50
○
A09 group Water supply parameters
A09.00 Set pressure
0.000~60.000Mpa
0.000
○
A09.01
Feedback full range max
pressure
0.000~60.000Mpa
1.000
○
A09.02 Lower limit pressure
0.000~60.000Mpa
0.000
○
A09.03 Upper limit pressure
0.000~60.000Mpa
1.000
○
A09.04 Wake up pressure
0.000~60.000Mpa
0.000
○
A09.05 Dormancy pressure
0.000~60.000Mpa
1.000
○
A09.06
Process time of feedback
pressure bigger than
dormancy pressure
0.0s~2500.0s
10.0
○
A09.07 Frequency dormancy
0.0Hz~max frequency (F00.06)
20.00
○
A09.08 Keep time of frequency lower
than dormancy frequency
0.0s~2500.0s
10.0
○