DOLD SAFEMASTER S UH 6932 Operating Instructions Manual Download Page 21

21

UH 6932 / 21.08.18 en / 010A

Reset the manual reset, automatic reset function

In the manual reset function mode, a reset input is provided for acknowledging 
error messages (over-speed and under-speed). Should a ‘T1’ status 
engage the input for longer than 1 second, then a reset will be conducted 
in the equipment. A renewed reset is however possible if the reset signal 
at the reset input is briefly interrupted. In the automatic reset mode, the 
input will be ignored because the above mentioned error message will be 
automatically reset.

Semiconductor outputs

The Semiconductor Output: 38 will indicate the status of the Relays: K1 
/ K2. When the relays are energized, then the Semiconductor Output: 38 
is switched on. The Semiconductor Output: 48 will report errors within the 
equipment. Should an error actually exist, then the Semiconductor Output: 
48 will be switched on.
The semiconductor outputs are not safety related. They can be used for 
monitoring purposes.

Setting the speed thresholds

For the monitoring functions: „internal window monitoring function“ and in 
the „external window monitoring function“, a minimum difference between 
the lower- and the upper -threshold of 5% is to be anticipated at the upper 
speed threshold, in addition to the already set hysteresis parameter. This 
is internally verified during the setting of the speed threshold and an error 
message will be displayed in case of any erroneous setting and/or the 
setting will not be permitted by the display. The maximum settable lower 
speed threshold can be calculated as follows:

Monitoring function: „Internal window monitoring“:
Maximum lower threshold = 
upper speed threshold - (5% + 2 x hysteresis) x upper speed threshold
Example:  
Upper speed threshold 100 Hz, hysteresis 2%
Maximum lower speed threshold =
100 Hz - (0.05 + 2 x 0.02) x 100 Hz = 91 Hz

Monitoring function: „External window monitoring:
Maximum speed threshold =
upper speed threshold - 5% x upper speed threshold
Example: 
Upper speed threshold 100 Hz, any required hysteresis
maximum lower speed threshold = 
100 Hz – 0.05 x 100 Hz = 95 Hz

Feedbak circuit

The feedback contacts of external contactors are monitored on terminal RF. 
The terminal RF gets the test signal from T2 via normally open contacts of 
the contactors which are connected to terminals 14 and 24. The normally 
closed contact have to be closed to start the device. If no contact extension 
or reinforcement is used, the terminals RF and T2 have to br bridged.

Start up time delay t

A

 

The start-up delay time period expires when switching-on the auxiliary 
voltage of the equipment, once the ‘RF’ feedback circuit is closed. In addition, 
the start-up delay time period will also expire after a reset in the manual 
reset mode. During this time period, no speed evaluation is conducted. The 
LED ‘t’ will flash and the output contacts: 13 to 14 and 23 to 24 will remain 
closed during this time period. As a result of the start-up delay time period, 
an alarm message can, for example be overridden during the start-up time 
period of a generator or electric motor. Should however, after a reset (in the 
manual reset mode), the feedback circuit not be closed, then the equipment 
will go into a safe error state.

Alarm delay t

v

  

The alarm-delay time period will expire when the equipment has recognised, 
that the speed exceed the permitted range. Only after the expiry of the 
alarm-delay time period, will the output contacts :13 to 14 and 23 to 24 be 
switched off. When the speed again enter the permitted range during the 
alarm-delay time period, then the alarm-delay function is terminated. The 
LED ‘t’ will flash during the time period.

Reset delay time t

F

 

The reset-delay time period represents the time during after which the 
output contacts: 13 to 14 and 23 to 24 are switched on (when the speed 
is within a permitted range). Should the speed again enter the alarm state 
during the runoff of the reset-delay time period (when the speed exceed the 
required range), the reset-delay time period will be terminated. The LED ‘t’ 
will flash during the same time period.
The start-up delay time period will override the reset-delay time period, 
i.e. when the output contacts are on by the start-up delay mode, then the 
reset-delay time period will be overridden (output contacts: 13 to 14 and 
23 to 24 are closed). Even after an expiry of the start-up delay time period, 
the reset-delay time period will not be initiated.

Display

In normal operating mode, all settings can be checked at any time by 
pressing the UP or DOWN keys. 
Additionally, the actula speed is displayed. However, this spped does not 
correspond to the device’s accuracy and is only designed for diagnostic 
purposes.
In the case of wiring errors and system failures corresponding diagnostic 
messages are displayed on the display.

Parameterization using the display

See attached form page 43

Change tracking

To detect non permitted changes of the settings, the menue item change 
tracking is available. This setting allows to activate a counter once, which 
is then incremented with each confirmed change of the settings. After ac-
tivation of this function the user cannot reset the counter or disable this 
function again.

Only at variant /_ _ 1

Digital selection via the software Inputs: SW1 to SW4

Four various speed modes with different response parameters, can be 
configured via the software Inputs: SW1 to SW4 (see Table). The electric 
power supply for the inputs should be between 10V DC and 26.4V DC 
to GND. A switchover configuration can also be undertaken during the 
operating mode. Should a speed mode be altered whilst operating, then the 
switchover time period (t

U

) will commence, provided the output relays are 

switched on through the switchover, and the start-up delay time period has 
expired. During this time period, no speed evaluation will be conducted and 
the output relays remain energized (closed). Should during the switchover 
time period the speed modus again be altered, then the switchover time 
will not again be initiated. After the expiry of the switchover time period, the 
monitoring function will be continued at the currently set speed mode). The 
switchover time period, for example can affect the overriding of an alarm 
message during the start-up stage- or the braking stage -of a generator 
or electric motor.
 

SW1

SW2

SW3

SW4

Mode  

Frequency mode 1  

Frequency mode 2

Frequency mode 3

Frequency mode 4

Caution !

!

  Any continuously repeated switching over of the speed modus 

(always immediately after the expiry of the switchover time 
period) can lead to the situation, that the equipment starts 
to function similarly as in the ‘Muting Mode’ (i.e. the speed 
monitoring function is overridden and the output relays remain 
permanently on).

Device and function description

Device and function description

Summary of Contents for SAFEMASTER S UH 6932

Page 1: ...EMASTER S Drehzahlw chter UH 6932 0272173 Datenblatt Betriebsanleitung DEUTSCH E DOLD S HNE KG Postfach 1251 78114 Furtwangen Deutschland Telefon 49 7723 6540 Fax 49 7723 654356 dold relays dold com w...

Page 2: ...schreibung 7 Ger te und Funktionsbeschreibung 8 Ger te und Funktionsbeschreibung 9 Technische Daten 10 UL Daten 10 Standardtype 11 Bestellbeispiel 11 Vorgehen bei St rungen 11 Fehlerbehandlung 11 Wart...

Page 3: ...tung GEFAHR GEFAHR Bedeutet dass Tod oder schwere K rperverletzung eintreten wird wenn die entsprechenden Vorsichtsma nahmen nicht ge troffen werden WARNUNG WARNUNG Bedeutet dass Tod oder schwere K rp...

Page 4: ...4 UH 6932 21 08 18 de 010A...

Page 5: ...ellbare Umschaltzeit von 0 100 s 0273534 Der Drehzahlw chter UH 6932 dient zur sicheren Drehzahl berwachung von Antrieben Er findet Anwendung in Maschinen und Anlagen bei de nen durch Maschinenbewegun...

Page 6: ..._1 Klemmenbezeichnung Signalbeschreibung A1 DC24V A2 0V U1 U2 Versorgung f r Initiatoren E1 E2 Messeing nge f r Initiatoren GND Bezugspotential f r Halbleiter Meldeausg nge und Steuerein g nge sowie...

Page 7: ...r Alarmverz gerungszeit werden die Ausgangskontakte 13 14 und 23 24 ausgeschaltet Geht die Drehzahl w hrend des Ablaufes der Alarmverz gerungszeit wieder in den Gutzustand wird die Alarmverz gerung ge...

Page 8: ...Minimalwert des Analogausgangs 2 V entspricht der eingestellten unteren Grenze Die Skalierung ist frequenzlinear In der berwachungsfunktion Unterfrequenz entspricht der Maximalwert desAnalogausgangsd...

Page 9: ...everz gerung 0 0 s Alarmverz gerung 0 1 s Umschalt berbr ckung 1 0 0 s Esc OK 1 5 Alarmspeicherung Alarmspeicherung x Automatischer Reset Esc OK 1 6 Mutingfunktion aktivieren deaktivieren x Esc OK Esc...

Page 10: ...ngsschutz Intern durch VDR Einschaltdauer Reset Taster 1 2 s Ausgang Kontaktbest ckung 2 Schlie er Kontaktart Relais zwangsgef hrt Thermischer Strom Ith 8 A siehe Summenstromgrenzkurve Schaltverm gen...

Page 11: ...terner Fehler genaue Fehler beschreibung siehe Display LED ERR leuchtet dauerhaft Ger tefehler wenn nach Neustart immer noch anliegt Ger t aus tauschen Werden am bzw im Ger t Fehler erkannt so werden...

Page 12: ...pr ft werden muss M10955 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND E1 M E2 U2 E2 GND GND E1 U1 M10996 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND...

Page 13: ...Reproduzierbarkeit 5 Anschlussspannung 10 30 V Restwelligkeit 10 Dauerstrom 200 mA 400 mA Ausgang 10 pnp NO 20 npn NO 10 pnp NO 20 npn NO Schaltstellungsanzeige LED Umgebungstemperatur 25 70 C Tempera...

Page 14: ...14 UH 6932 21 08 18 de 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Postfach 1251 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Page 15: ...S Speed Monitor UH 6932 Datasheet Operating Instructions ENGLISH E DOLD S HNE KG P O Box 1251 D 78114 Furtwangen Germany Tel 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com Translati...

Page 16: ...ion 22 Device and function description 23 Technical Data 24 UL Data 24 Standard Type 25 Ordering Example 25 Troubleshooting 25 Fault handling 25 Maintenance and repairs 25 Characteristic 25 Applicatio...

Page 17: ...r documen tation of the setting parameters Opening the device or implementing unauthorized changes voids any warranty DANGER DANGER Indicates that death or severe personal injury will result if proper...

Page 18: ...18 UH 6932 21 08 18 en 010A...

Page 19: ...t analog output 2 V to 10 V corresponding to the current speed the possibility of overriding the speed by a supervisory function muting adjustable switchover time from 0 100 s 0273535 The speed monito...

Page 20: ...ange of both the upper and lower response parameters minus and or plus the pre set hysteresis values upper response parameter minus and or the lower response parameter plus the relative hysteresis val...

Page 21: ...d range Only after the expiry of the alarm delay time period will the output contacts 13 to 14 and 23 to 24 be switched off When the speed again enter the permitted range during the alarm delay time p...

Page 22: ...is equal to the adjusted upper frequency threshold The minimum value of the analogue output 2 V is equal to the adjusted lower frequency threshold The scaling is frequency linear In the monitoring fu...

Page 23: ...ay Start up delay 0 0 s Response delay 0 0 s Alarm delay 0 1 s Changeover bridging 1 0 0 s Esc OK 1 5 Alarm memory Alarm memory x automatic reset Esc OK 1 6 Muting function activate deactivate x Esc O...

Page 24: ...ction Internal PTC Overvoltage protection Internal VDR Duty cycle Reset button 1 2 s Output Contacts 2 NO contacts Contact type Relay forcibly guide Thermischer Strom Ith 8 A see current limit curve S...

Page 25: ...r restart the device must be replaced and sent back to manufacturer Failure Potential cause LED ON does not light up Power supply A1 A2 not connected LED ON flashes red Parameterization error detailed...

Page 26: ...base M10955 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND E1 M E2 U2 E2 GND GND E1 U1 M10996 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND E1 M U2 E2 GN...

Page 27: ...t accuracy 5 Voltage range 10 30 V Residual ripple 10 Continuous current 200 mA 400 mA Output 10 pnp NO 20 npn NO 10 pnp NO 20 npn NO Indication of output state LED Ambient temperature 25 70 C Tempera...

Page 28: ...28 UH 6932 21 08 18 en 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com POBox1251 Telephone 49 7723 654 0 Telefax 49 77 23 654 356...

Page 29: ...leur de vitesse de rotation UH 6932 Fiche Technique Manuel d utilisation FRAN AIS E DOLD S HNE KG B P 1251 78114 Furtwangen Allemagne T l 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold...

Page 30: ...fonctions 35 Description de l appareil et des fonctions 36 Description de l appareil et des fonctions 37 Caract ristiques techniques 38 Donn es UL 38 Version standard 39 Exemple de commande 39 Diagnos...

Page 31: ...ures graves vont survenir en cas de non respect des pr cautions demand es AVERTISSEMENT AVERTISSEMENT Indique que la mort ou des blessures graves peuvent survenir si les pr cautions appropri es ne son...

Page 32: ...32 UH 6932 21 08 18 fr 010A...

Page 33: ...tation actuelle possibilit d inhiber la surveillance de vitesse de rotation Muting Temporisation de commutation r glable 0 100 s 0273536 Description du produit Le relais de contr le de rotation UH 693...

Page 34: ...sation de d marrage tF Dans la fonction de surveillance sous vitesse de rotation le relais de sortie passe dans la position d alarme quand la valeur de r ponse r gl e plus longue que la temporisation...

Page 35: ...temporisation d alarme se d roule apr s que l appareil a reconnu que la vitesse de rotation fr quence se trouve en dehors de l tat normal Seulement apr s l coulement de la temporisation d alarme les c...

Page 36: ...rrespond la valeur maximale du seuil de fr quence r gl La valeur minimale 2 V de la valeur analogique correspond la valeur minimale du seuil de fr quence r gl L chelle est lin aire en fr quence En fon...

Page 37: ...s Temporisation de r sponse 0 0 s Temporisation d alarme 0 1 s Pontage commut 1 0 0 s Esc OK 1 5 M moire alarme M moire alarme x R set automatique Esc OK 1 6 Fonction muting activer d sactiver x Esc...

Page 38: ...Facteur de marche BP Reset 1 2 s Sortie Garnissage en contacts 2 contacts NO Type de contact Relais li Courant thermique Ith 8 A voir courbe limite de totalisation de courant Pouvoir de coupure en AC...

Page 39: ...tecte une erreur le message correspondant s affiche sur l cran Lorsqu il est n cessaire de r initialiser l appareil en raison d une erreur l erreur et le message de diagnostic correspondant doivent tr...

Page 40: ...s de la fonction de s curit M10955 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND E1 M E2 U2 E2 GND GND E1 U1 M10996 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5...

Page 41: ...t 5 Tension de raccord 10 30 V Ondulation r siduelle 10 Courant continu 200 mA 400 mA Sortie 10 pnp NO 20 npn NO 10 pnp NO 20 npn NO Affichage des pos de couplage LED Temp rature ambiante 25 70 C D ri...

Page 42: ...42 UH 6932 21 08 18 fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com B P 1251 T l phone 49 77 23 654 0 T l fax 49 77 23 654 356...

Page 43: ...Demontage der steckbaren Klemmenbl cke Stecker 1 Ger t spannungsfrei schalten 2 Schraubendreher in die frontseitige Aussparung zwischen Stecker und Frontplatte hineinschieben 3 Schraubendreher um sein...

Page 44: ...EN 61511 SIL CL 3 IEC EN 62061 SIL 3 IEC EN 61508 IEC EN 61511 HFT 1 DC 99 0 PFHD 1 8E 10 h 1 PFDAVG 8 1E 05 Low Demand Mode T1 20 a year HFT Hardware Fehlertoleranz Hardware failure tolerance Tol ran...

Page 45: ...45 UH 6932 21 08 18 de en fr 010A DE EG Konformit tserkl rung EN CE Declaration of Conformity FR D claration de conformit europ enne...

Page 46: ...46 UH 6932 21 08 18 de en fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Postfach 1251 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Page 47: ...en deaktivieren Esc OK Esc OK Bitte heraustrennen und sicher aufbewahren Parametrierung anhand des Displays Um in den Parametriermodus des Ger tes zu gelangen ist folgende Tastenkombination vorgesehen...

Page 48: ...48 UH 6932 21 08 18 de en fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Page 49: ...ting function activate deactivated Esc OK Esc OK Please cut off and file it Parameterization using the display To enter the device s parameterization mode the following key combination is provided Pre...

Page 50: ...50 UH 6932 21 08 18 de en fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com POBox1251 Telephone 49 7723 654 0 Telefax 49 7723 654 356...

Page 51: ...tiver Esc OK Esc OK Veuillez d couper cette feuille et la conserver avec soin Param trage l aide de l cran La combinaison de touches suivante est pr vue pour activer le mode param trage de l appareil...

Page 52: ...52 UH 6932 21 08 18 de en fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com B P 1251 T l phone 49 77 23 654 0 T l fax 49 77 23 654 356...

Reviews: