DOLD SAFEMASTER S UH 6932 Operating Instructions Manual Download Page 20

20

UH 6932 / 21.08.18 en / 010A

LED ON:  

green 

On, when supply connected

 

green-flashing 

Parameterization mode

 

red-flashing 

Parameterization error

LED K1/K2:   green 

Relay K1 and K2 energized 

 

yellow 

Muting (Relay K1 and K2 energized)

 

LED ERR:   red  

Internal failure

 

red-flashing 

External failure

LED t:  

green-flashing 

(K1/K2; light up) 

 

 

Expiry of the delay time periods t

A

 or t

U

 

yellow-flashing 

(K1/K2 does not light up)

 

 

Expiry of the delay time periods t

F

 

yellow-flashing 

(K1/K2 light up) 

 

 

Expiry of the delay time periods t

V

DISPLAY: 

 

Status indication

 

 

Alarms / diagnostics

  

Parameterization 

The auxiliary voltage is connected to terminals A1 to A2. The equipment 
can be configured via the display and the setting keys on the front plate. 
The detection of the speed is effected via two NPN- or PNP-proximity 
switches, which are connected up at the Inputs: E1 and E2. The electric 
power supply for the proximity switch is provided from the speed monitor 
of 24V DC at the Terminals: U1 and U2. For each initiator a separate wire 
has to be used and wired separately. The input speed are compared in-
ternally to the thresholds already set on the equipment. As the internally 
measures the time periods, the fastest possible speed detection monito-
ring is possible. Should the over-speed function be set, then the output 
relay will switch to the alarm mode, when the set response parameter 
is over-exceeded longer than the parametered alarm-delay function (t

V

). 

Should the speed fall again below the response parameter, minus the set 
hysteresis, the output relay will be activated after the expiry of the reset-
delay time period (t

F

) and return to its pre-set permitted supervisory state. 

As regards the under-speed function, the output relay will switch to the 
alarm mode, when the set response parameter is under-exceeded longer 
than the parametered alarm-delay function (t

V

) time period. As soon as 

the speed return to the range governed by the response parameter, plus 
the set hysteresis, then the output relay will again return to the pre-set 
permitted state after the expiry of the reset-delay time period (t

F

). In the 

„internal window function mode“, the output relay will switch to the alarm 
setting when the speed exceed the pre-set permitted range of the res-
ponse parameter. Once the speed again return within the range of both 
the upper- and lower response parameters, minus and/or plus the pre-
set hysteresis values (upper response parameter minus- and/or the lower 
response parameter plus -the relative hysteresis values), then the output 
relay will again switch back to the pre-set permitted range after the expiry 
of the reset-delay time period (t

F

). 

M10956_b

T2

38

RF

48

13 23

14 24

K1

K2

RES

A2

T1

GND

GND

A1

+

U2

GND

E2

U1

GND

E1

24

14

13

23

UH 6932

M10954_b

T2

38

RF

48

13 23

14 24

K1

K2

RES

T1

SW3

SW2

SW1

SW4

A

+

A

GND

A2 GND

A1

+

U2

GND

E2

U1

GND

E1

24

14

13

23

UH 6932/_ _1

Terminal designation

Signal designation

A1+

DC24V

A2

0V

U1, U2

(+) supply for proximity sensors

E1, E2

measuring inputs for proximity sensors

GND

Reference potential for 
Semiconductor monitoring output 
and control outputs, as well as (-) 
supply for proximity sensors

13, 14, 23, 24

Forcibly guided NO contacts for 
release circuit

38, 48

Semiconductor-monitoring output

T1, T2

Control output

RES, RF, SW1, SW2, SW3, SW4

Control input

A +, A GND

Analogue output

In the „external window function mode“, the monitoring function acts inver-
sely to the „internal window function“. Should the manual reset function be 
activated, then the output relay continues to remain in the alarm setting 
when the speed return to the pre-set permitted range. A resetting of the 
saved parameter is possible when the reset input is activated or the auxi-
liary voltage is shutdown. 
When a start-up delay time (t

A

) is set, then the set start-up delay time will 

initially expire as soon as the auxiliary voltage of the equipment is swit-
ched-on and the ‘RF’ feedback circuit is closed. The start-up delay time will 
also expire after a reset of the manual reset mode. During this time period, 
a speed evaluation is disabled and the output relays remain at the pre-set 
permitted setting. The start-up delay function can, for example override an 
alarm message during the start-up stage of a generator or electric motor. 
Should, after a reset (in the manual reset mode), the feedback circuit not 
be closed, then the equipment will go into a safe error state.

With correct connection it is possible to realise with the UH 6932 the 

safety functions STO (Safe Torque Off), SOS (Safe Operating Stop), 

SLS (Safely Limited Speed), SSM (Safe Speed Monitor) and SSR (Safe 

Speed Range) according to EN 61800-5-2. The actual realisation of the 

safety functions has to be validated in each application of the product for 

safety aspects.

Circuit Diagrams

Functions

Functions

Indicators

Connection Terminals

Summary of Contents for SAFEMASTER S UH 6932

Page 1: ...EMASTER S Drehzahlw chter UH 6932 0272173 Datenblatt Betriebsanleitung DEUTSCH E DOLD S HNE KG Postfach 1251 78114 Furtwangen Deutschland Telefon 49 7723 6540 Fax 49 7723 654356 dold relays dold com w...

Page 2: ...schreibung 7 Ger te und Funktionsbeschreibung 8 Ger te und Funktionsbeschreibung 9 Technische Daten 10 UL Daten 10 Standardtype 11 Bestellbeispiel 11 Vorgehen bei St rungen 11 Fehlerbehandlung 11 Wart...

Page 3: ...tung GEFAHR GEFAHR Bedeutet dass Tod oder schwere K rperverletzung eintreten wird wenn die entsprechenden Vorsichtsma nahmen nicht ge troffen werden WARNUNG WARNUNG Bedeutet dass Tod oder schwere K rp...

Page 4: ...4 UH 6932 21 08 18 de 010A...

Page 5: ...ellbare Umschaltzeit von 0 100 s 0273534 Der Drehzahlw chter UH 6932 dient zur sicheren Drehzahl berwachung von Antrieben Er findet Anwendung in Maschinen und Anlagen bei de nen durch Maschinenbewegun...

Page 6: ..._1 Klemmenbezeichnung Signalbeschreibung A1 DC24V A2 0V U1 U2 Versorgung f r Initiatoren E1 E2 Messeing nge f r Initiatoren GND Bezugspotential f r Halbleiter Meldeausg nge und Steuerein g nge sowie...

Page 7: ...r Alarmverz gerungszeit werden die Ausgangskontakte 13 14 und 23 24 ausgeschaltet Geht die Drehzahl w hrend des Ablaufes der Alarmverz gerungszeit wieder in den Gutzustand wird die Alarmverz gerung ge...

Page 8: ...Minimalwert des Analogausgangs 2 V entspricht der eingestellten unteren Grenze Die Skalierung ist frequenzlinear In der berwachungsfunktion Unterfrequenz entspricht der Maximalwert desAnalogausgangsd...

Page 9: ...everz gerung 0 0 s Alarmverz gerung 0 1 s Umschalt berbr ckung 1 0 0 s Esc OK 1 5 Alarmspeicherung Alarmspeicherung x Automatischer Reset Esc OK 1 6 Mutingfunktion aktivieren deaktivieren x Esc OK Esc...

Page 10: ...ngsschutz Intern durch VDR Einschaltdauer Reset Taster 1 2 s Ausgang Kontaktbest ckung 2 Schlie er Kontaktart Relais zwangsgef hrt Thermischer Strom Ith 8 A siehe Summenstromgrenzkurve Schaltverm gen...

Page 11: ...terner Fehler genaue Fehler beschreibung siehe Display LED ERR leuchtet dauerhaft Ger tefehler wenn nach Neustart immer noch anliegt Ger t aus tauschen Werden am bzw im Ger t Fehler erkannt so werden...

Page 12: ...pr ft werden muss M10955 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND E1 M E2 U2 E2 GND GND E1 U1 M10996 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND...

Page 13: ...Reproduzierbarkeit 5 Anschlussspannung 10 30 V Restwelligkeit 10 Dauerstrom 200 mA 400 mA Ausgang 10 pnp NO 20 npn NO 10 pnp NO 20 npn NO Schaltstellungsanzeige LED Umgebungstemperatur 25 70 C Tempera...

Page 14: ...14 UH 6932 21 08 18 de 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Postfach 1251 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Page 15: ...S Speed Monitor UH 6932 Datasheet Operating Instructions ENGLISH E DOLD S HNE KG P O Box 1251 D 78114 Furtwangen Germany Tel 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com Translati...

Page 16: ...ion 22 Device and function description 23 Technical Data 24 UL Data 24 Standard Type 25 Ordering Example 25 Troubleshooting 25 Fault handling 25 Maintenance and repairs 25 Characteristic 25 Applicatio...

Page 17: ...r documen tation of the setting parameters Opening the device or implementing unauthorized changes voids any warranty DANGER DANGER Indicates that death or severe personal injury will result if proper...

Page 18: ...18 UH 6932 21 08 18 en 010A...

Page 19: ...t analog output 2 V to 10 V corresponding to the current speed the possibility of overriding the speed by a supervisory function muting adjustable switchover time from 0 100 s 0273535 The speed monito...

Page 20: ...ange of both the upper and lower response parameters minus and or plus the pre set hysteresis values upper response parameter minus and or the lower response parameter plus the relative hysteresis val...

Page 21: ...d range Only after the expiry of the alarm delay time period will the output contacts 13 to 14 and 23 to 24 be switched off When the speed again enter the permitted range during the alarm delay time p...

Page 22: ...is equal to the adjusted upper frequency threshold The minimum value of the analogue output 2 V is equal to the adjusted lower frequency threshold The scaling is frequency linear In the monitoring fu...

Page 23: ...ay Start up delay 0 0 s Response delay 0 0 s Alarm delay 0 1 s Changeover bridging 1 0 0 s Esc OK 1 5 Alarm memory Alarm memory x automatic reset Esc OK 1 6 Muting function activate deactivate x Esc O...

Page 24: ...ction Internal PTC Overvoltage protection Internal VDR Duty cycle Reset button 1 2 s Output Contacts 2 NO contacts Contact type Relay forcibly guide Thermischer Strom Ith 8 A see current limit curve S...

Page 25: ...r restart the device must be replaced and sent back to manufacturer Failure Potential cause LED ON does not light up Power supply A1 A2 not connected LED ON flashes red Parameterization error detailed...

Page 26: ...base M10955 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND E1 M E2 U2 E2 GND GND E1 U1 M10996 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND E1 M U2 E2 GN...

Page 27: ...t accuracy 5 Voltage range 10 30 V Residual ripple 10 Continuous current 200 mA 400 mA Output 10 pnp NO 20 npn NO 10 pnp NO 20 npn NO Indication of output state LED Ambient temperature 25 70 C Tempera...

Page 28: ...28 UH 6932 21 08 18 en 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com POBox1251 Telephone 49 7723 654 0 Telefax 49 77 23 654 356...

Page 29: ...leur de vitesse de rotation UH 6932 Fiche Technique Manuel d utilisation FRAN AIS E DOLD S HNE KG B P 1251 78114 Furtwangen Allemagne T l 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold...

Page 30: ...fonctions 35 Description de l appareil et des fonctions 36 Description de l appareil et des fonctions 37 Caract ristiques techniques 38 Donn es UL 38 Version standard 39 Exemple de commande 39 Diagnos...

Page 31: ...ures graves vont survenir en cas de non respect des pr cautions demand es AVERTISSEMENT AVERTISSEMENT Indique que la mort ou des blessures graves peuvent survenir si les pr cautions appropri es ne son...

Page 32: ...32 UH 6932 21 08 18 fr 010A...

Page 33: ...tation actuelle possibilit d inhiber la surveillance de vitesse de rotation Muting Temporisation de commutation r glable 0 100 s 0273536 Description du produit Le relais de contr le de rotation UH 693...

Page 34: ...sation de d marrage tF Dans la fonction de surveillance sous vitesse de rotation le relais de sortie passe dans la position d alarme quand la valeur de r ponse r gl e plus longue que la temporisation...

Page 35: ...temporisation d alarme se d roule apr s que l appareil a reconnu que la vitesse de rotation fr quence se trouve en dehors de l tat normal Seulement apr s l coulement de la temporisation d alarme les c...

Page 36: ...rrespond la valeur maximale du seuil de fr quence r gl La valeur minimale 2 V de la valeur analogique correspond la valeur minimale du seuil de fr quence r gl L chelle est lin aire en fr quence En fon...

Page 37: ...s Temporisation de r sponse 0 0 s Temporisation d alarme 0 1 s Pontage commut 1 0 0 s Esc OK 1 5 M moire alarme M moire alarme x R set automatique Esc OK 1 6 Fonction muting activer d sactiver x Esc...

Page 38: ...Facteur de marche BP Reset 1 2 s Sortie Garnissage en contacts 2 contacts NO Type de contact Relais li Courant thermique Ith 8 A voir courbe limite de totalisation de courant Pouvoir de coupure en AC...

Page 39: ...tecte une erreur le message correspondant s affiche sur l cran Lorsqu il est n cessaire de r initialiser l appareil en raison d une erreur l erreur et le message de diagnostic correspondant doivent tr...

Page 40: ...s de la fonction de s curit M10955 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5 Reset GND E1 M E2 U2 E2 GND GND E1 U1 M10996 RF K5 K4 23 RES 14 A2 24 13 A1 UH6932 T2 T1 48 38 K4 N L K5...

Page 41: ...t 5 Tension de raccord 10 30 V Ondulation r siduelle 10 Courant continu 200 mA 400 mA Sortie 10 pnp NO 20 npn NO 10 pnp NO 20 npn NO Affichage des pos de couplage LED Temp rature ambiante 25 70 C D ri...

Page 42: ...42 UH 6932 21 08 18 fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com B P 1251 T l phone 49 77 23 654 0 T l fax 49 77 23 654 356...

Page 43: ...Demontage der steckbaren Klemmenbl cke Stecker 1 Ger t spannungsfrei schalten 2 Schraubendreher in die frontseitige Aussparung zwischen Stecker und Frontplatte hineinschieben 3 Schraubendreher um sein...

Page 44: ...EN 61511 SIL CL 3 IEC EN 62061 SIL 3 IEC EN 61508 IEC EN 61511 HFT 1 DC 99 0 PFHD 1 8E 10 h 1 PFDAVG 8 1E 05 Low Demand Mode T1 20 a year HFT Hardware Fehlertoleranz Hardware failure tolerance Tol ran...

Page 45: ...45 UH 6932 21 08 18 de en fr 010A DE EG Konformit tserkl rung EN CE Declaration of Conformity FR D claration de conformit europ enne...

Page 46: ...46 UH 6932 21 08 18 de en fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Postfach 1251 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Page 47: ...en deaktivieren Esc OK Esc OK Bitte heraustrennen und sicher aufbewahren Parametrierung anhand des Displays Um in den Parametriermodus des Ger tes zu gelangen ist folgende Tastenkombination vorgesehen...

Page 48: ...48 UH 6932 21 08 18 de en fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Page 49: ...ting function activate deactivated Esc OK Esc OK Please cut off and file it Parameterization using the display To enter the device s parameterization mode the following key combination is provided Pre...

Page 50: ...50 UH 6932 21 08 18 de en fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com POBox1251 Telephone 49 7723 654 0 Telefax 49 7723 654 356...

Page 51: ...tiver Esc OK Esc OK Veuillez d couper cette feuille et la conserver avec soin Param trage l aide de l cran La combinaison de touches suivante est pr vue pour activer le mode param trage de l appareil...

Page 52: ...52 UH 6932 21 08 18 de en fr 010A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com B P 1251 T l phone 49 77 23 654 0 T l fax 49 77 23 654 356...

Reviews: