46
DC-ITD-CL4andCL8MAN01.A
www.dodtec.com
NOV 2018
815-788-5200
CL4 & CL8 Manual
Appendix B
–
I/O Connection Detail
B.1 Standard Output Relay Module
Description
Output
Point 1 Alarm Level 1
0
Point 1 Alarm Level 2
1
Point 2 Alarm Level 1
2
Point 2 Alarm Level 2
3
Point 3 Alarm Level 1
4
Point 3 Alarm Level 2
5
Point 4 Alarm Level 1
6
Point 4 Alarm Level 2
7
Point 5 Alarm Level 1
8
Point 5 Alarm Level 2
9
Point 6 Alarm Level 1
10
Point 6 Alarm Level 2
11
Point 7 Alarm Level 1
12
Point 7 Alarm Level 2
13
Point 8 Alarm Level 1
14
Point 8 Alarm Level 2
15
Critical Fault
16
Watchdog
17
Power On
18
Analysis Mode
19
General Fault
20
Gas Alarm Level 1
21
Gas Alarm Level 2
22
Critical Fault (*)
23
General Fault (*)
24
Gas Alarm Level 1 (*)
25
Gas Alarm Level 2 (*)
26
Blue Light
27
Audible Alarm
28
Green Light
29
Orange Light
30
Red Light
31
(* ) Can be Energized / De-Energized
Output Relay Connector
0
1
O
utpu
t
2
3
4
5
6
7
8
9
10
11
12
13
14
15
V1 +
V1 -
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
V2 +
V2 -
Connect 24 Volt supply to V1 +/- and V2
+/-. (See Connector diagram.)
Outputs 0-15 use common ground (V1 -)
Outputs 16-31 use common ground (V2
-)
0.2 Amp per output max current
Outputs 0-15 Max current 1.6A