33
DC-ITD-CL4andCL8MAN01.A
www.dodtec.com
NOV 2018
815-788-5200
CL4 & CL8 Manual
5.3 Concentration Log
Touching the ‘CONC LOG’ button on the Event History screen (section 5.2.
9) will bring up the screen shown in
figure 5.13.
Figure 5.13
The log displays the concentration on each point when the trigger criteria is met. If you select >0 the system
will log all CL4/CL8 points when any of the points have a concentration reading which is >LDL for the gas
selected. (See appendix E).
The buttons on the right of the screen allow scrolling through the most recently logged readings. Touch the
configuration button to set the logging parameters.
5.3.1 Concentration Configuration
Figures 5.12.b shows the concentration configuration screen. Four levels of logging area available
depending on your needs.
1.
Alarm Level 2
–
Logging on when any channel is above alarm level 2
2.
Alarm Level 1
–
Logging on when any channel is above alarm level 1.
3.
0
–
Logging on when any channel is above 0
4.
Continuous
–
Logging always on (not recommended)
Figure 5.12b
Page Up
Up 1 message
Go to last message
Down 1 message
Page Down
See section 5.5
Current
log file
name
Go to Concentration configuration Page (See section
5.3.1)
See section 5.6