Digital Monitoring Products
iComSL
Series Universal Communicator Installation and Programming Guide
16
11.5
Power Fail Delay
This option tracks the duration of a primary power failure. The delay time can be from 1
to 9 hours. When the power is off for the length of the programmed delay time, a power
failure report is sent to the receiver. For example, if the power failure delay is set for
two hours, then the power failure report will be sent between 2-3 hours. Entering a 0
(zero) sends the power failure report within 15 seconds.
11.6
Swinger Bypass Trips
Enter the number of times (1-6) a zone can go into an alarm or trouble condition within
one hour be fore being auto matically bypassed. Bypassed zones are auto matically reset
when the area they are assigned to is disarmed. All 24-hour zones are reset when any
area of the system is dis armed. A programming Stop operation restores a bypassed zone.
Entering 0 (zero) disables this function. Default is 2.
How it works
The communicator
hour timer starts at 59 minutes past the hour. If the hour timer
expires before the trip counter is exceeded, the trip counter returns to 0 (zero). If the
trip counter is exceeded before the hour expires, the zone is auto matically bypassed by
the communicator
. A Bypass Re port is sent to the receiver if Bypass Re ports is YES.
11.7
Reset Swinger Bypass
When YES is selected, an auto matically bypassed zone is reset if it remains in a normal
condition for one complete hour after being bypassed. A report of the automatic reset is
sent to the receiver if Bypass Reports has been se lected as YES. Default is NO.
11.8
Time Changes
This option allows the communicator
to request automatic time changes from the DMP
SCS-1R or SCS-VR
Receiver. For the receiver to send time changes, it must be
programmed to send time changes and must be receiving time change updates from the
host automation computer at least every 24 hours. Default is YES.
When time zone is programmed YES, enter the number (0-23) that indicates the
Greenwich Mean Time zone (GMT) where the
communicator is located. The default is 6.
See table below for GMT values.
GMT
City/Time Zone
GMT
City/Time Zone
0
London, Monrovia, Lisbon
12
Fiji, Marshall Island, Wellington
1
Cape Verde Island, Azores
13
New Cadelonia
2
Mid-Atlantic
14
Guam, Sydney
3
Buenos Aires, Georgetown
15
Tokyo, Seoul
4
Atlantic Time (Canada), Caracas
16
Hong Kong, Singapore
5
Eastern Time (US, Canada) Bogota
17
Bangkok, Hanoi
6
Central Time (US, Canada) Saskatchewan
18
Dhaka, Almaty
7
Mountain Time (US, Canada), Edmonton
19
Islamabad, Karachi
8
Pacific Time (US, Canada), Tijuana
20
Abu Dhabi, Kazan
9
Alaska
21
Moscow, Bagdad
10
Hawaii
22
Eastern Europe
11
Midway Island, Samoa
23
Rome, Paris, Berlin
11.9
Keypad Input
This option allows the iComSL to communicate with Ademco/Honeywell panels over the
Ademco/Honeywell ECP Bus using the zone 4 + and zone 4 - terminals.
This allows the communicator to add and delete User Codes as well as Arm and Disarm
the Ademco/Honeywell panel.
Note:
Existing user codes in the Ademco/Honeywell panel must be entered in the
iComSL. Any new user codes entered in the iComSL will also be entered in the Ademco/
Honeywell as well.
Select ECP to enable communication. When NONE is selected, zone 4 functions as a Bell
input. Default is NONE.
See Figure 19: Ademco Vista 20P ECP to iComSL
for additional information.
PWR FAIL HRS:
1
SWGRBYPS TRIPS: 2
RST SBYP NO YES
TIME CHG NO YES
HRS FROM GMT:
6
KYPD INPUT
NONE ECP
system optIons