Output Wiring

Before  connecting  an  output  device  (actuator,  relay,  etc.)  to  the  controller,  refer  to  the  datasheet  and  installation
guide of the equipment manufacturer.

£

For a wire length less than 75’ (23m) long, either a shielded or unshielded 18AWG wire may be used.

£

For a wire length up to 200’ (61m) long, a shielded 18AWG wire is recommended.

£

The shield of the wire should be grounded on the controller side and the shield length should be kept as short
as possible.

£

For relay outputs (DOx); select appropriately-sized wiring suitable to the current load.

£

To measure the state of a triac output, an external load must be connected.

Table 3 shows the ECB-203, ECB-300, ECB-400, and ECB-600 Series controller Output and Jumper support. Table 4 shows the available output wiring
methods.

Controller

Digital (Triac) Outputs

Universal Outputs

Jumper

0 to 10VDC/0 to 20mA

ECB‑203

5

3

ECB‑300

0

8

ECB‑4x0 Series

0

12

ECB‑4x3 Series

8

4

ECB‑600 Series

0

12

Table 3: Controller Output Support

Control Output Type

Output Designation

Output Connection Diagram

£

Discrete 0 or 12VDC digital, Pulse, or PWM output controlling
a  12VDC  relay.  Maximum  60  mA  (minimum  load  resistance
200Ω).

UOx

From 

Digital 

Output

12VDC Relay

A1

A2

UOx

COM

£

Current 0 to 20mA universal output & jumper configuration

£

For ECB-300, ECB-400, and ECB-600 Series only

£

For jumper location, see Jumper Identification and Configura-
tion.

UOx

0-20mA

Common

From Digital-To-

Analog Output

UOx

COM

JUMPER

SETTING

0-10V

0-20mA

£

Linear 0 to 10VDC digital to analog output.

UOx

0-10V

Common

From Digital-

To-Analog 

Output

UOx

COM

£

0 to 10VDC voltage output controlling an analog actuator that
is powered by an external 24VAC power source.

UOx

0-10V

~ or +

From Digital-

To-Analog 

Output

UOx

COM

Actuator

or -

24VAC

£

24VAC  externally-powered  triac  output  controlling  a  floating
actuator

1

.

£

Ensure that the external power supply is grounded as shown.

DOx

Actuator

~

~

24VAC

DOy

Cx

DOx

Cy

£

24VAC controller-powered triac output controlling a relay

1

 with

line and neutral switching.

£

Ensure  that  the  transformer’s  secondary  winding  is  grounded
as shown.

DOx

DOx

Cx

24VAC Relay

A2

A1

      Transformer

24VAC

24VCOM

AC

Electrical 
System Ground

Fuse: 4A Max.

Fast Acting

Controller

24VAC

Load

DOx

Cx

24VAC Relay

A2

A1

      Transformer

24VAC

24VCOM

AC

Electrical 
System Ground

Fuse: 4A Max.

Fast Acting

Controller

24VAC

Load

Line Switching

Neutral Switching

Summary of Contents for Allure ECB-400 Series

Page 1: ...tion and subsequent operation of the device pay special attention to the following recommendations It is recommended that the controller s be kept at room temperature for at least 24 hours before inst...

Page 2: ...e Hardware Installation Guide Alternating Current Direct Current General Wiring Recommendations Risk of Electric Shock Turn off power before any kind of servicing to avoid electric shock All wiring mu...

Page 3: ...3 20 Controller Dimensions Components Figure 2 Rear view of large enclosure Figure 3 Rear view of small enclosure Figure 4 Side view of large and small enclosure...

Page 4: ...orientation must be horizontal with controller s back attached to a vertical wall surface Figure 5 Permitted Mounting Positions DIN Rail Mounted Installation 1 Ensure the DIN rail is properly mounted...

Page 5: ...ted to the grounded transformer terminal as shown below This ensures that the 24V COM terminals of all devices connected to any BACnet MS TP bus in the building are at the same potential Always use a...

Page 6: ...et Port Wireless Port Universal Inputs UI 0 20 mA Enable Disable 0 20 mA Disable 0 20mA Enable Figure 9 ECB 300 Controller Jumper Locations Factory default positions BACnet MS TP Network Board BACnet...

Page 7: ...6 Table 1 Controller Input Support Sensor Input Type Input Connection Diagram Dry Contact input UIx COM To Digital Input Digital Dry Contact NO NC RTD input for example 1000 Thermistor Input for examp...

Page 8: ...ge input used with a 0 to 10VDC or 0 to 5VDC sensor powered by its own power source 0 10V Sensor UIx COM To Analog To Digital Converter Slow Pulse Internal supply 2 wire pulse meter for ECB 203 ECB 30...

Page 9: ...PWM output controlling a 12VDC relay Maximum 60 mA minimum load resistance 200 UOx From Digital Output 12VDC Relay A1 A2 UOx COM Current 0 to 20mA universal output jumper configuration For ECB 300 EC...

Page 10: ...the cable and attaching it to a solid object with a nylon tie so that a tug on the cable will not pull out the connector on the controller Subnet Wiring with the ECB 600 Series Controller ECx 400 ser...

Page 11: ...e information and requirements to implement a BACnet MS TP network It contains information about network plan ning and MAC Address numbering schemes It can be downloaded from the www distech controls...

Page 12: ...S TP Adaptor to the NET PORT au dio plug Wire a standard 3 5 mm three conductor stereo jack as shown below The BACnet MS TP Adaptor must have an electrically isolated RS 485 port Otherwise a ground pa...

Page 13: ...Press and hold the Menu button for 5 seconds to enter the password menu 10000 is shown on the display OR Screen Timeout 15 seconds 3 Press the down button to set the number to 9995 this is the defaul...

Page 14: ...ut 15 seconds 3 Use the down button to set the number to 9995 this is the default password OR Screen Timeout 15 seconds 4 Press the Menu button to submit the password Upon submitting the password the...

Page 15: ...r s BAUD rate as follows 1 Connect an Allure EC Smart Vue Series Communicating Sensor sensor to the controller with a Cat 5e patch cable Wait for the display to show the room temperature 2 Press and h...

Page 16: ...telephone socket Connecting to the Controller s Wireless Port Each controller has a wireless port in which one end of the Wireless Receiver s telephone cable plugs in Strain relief and Terminal Block...

Page 17: ...ser s authority to operate the equipment This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed...

Page 18: ...Fast Acting Electrical System Ground Data Bus Shields Twist together and Isolate with electrical tape From Previous Device To Next Device BACnet MS TP Network ECB 400 249 ohm resistor built in for in...

Page 19: ...DIP switch on the faceplate or under the cover of the controller If it is set to 0 all off use an Allure EC Smart Vue sensor to check the MAC Address There is another controller with the same Device...

Page 20: ...The device has not received a BACnet token and therefore cannot communicate on the network Verify that the controller s MAC Address is unique on the BACnet MS TP Data Bus see Device Addressing Make su...

Reviews: