background image

19 / 20

Troubleshooting Guide

Controller is powered but does not turn on

Fuse has blown

Disconnect the power. Check the fuse integrity. Reconnect the power.

Power supply polarity

Verify that consistent polarity is maintained between all controllers and the transformer. Ensure that the 24VCOM terminal of
each controller is connected to the same terminal on the secondary side of the transformer. See 

Power Wiring.

Controller cannot communicate on a BACnet MS/TP network

Absent or incorrect supply voltage

1. Check power supply voltage between 24VAC ±15% and 24VCOM pins and ensure that it is within acceptable limits.

2. Check for tripped fuse or circuit breaker.

Overloaded power transformer

Verify that the transformer used is powerful enough to supply all controllers.

Network not wired properly

Double check that the wire connections are correct.

Absent or incorrect network termination

Check the network termination(s).

Max Master parameter

Configure  the  maximum  number  of  master  device  on  the  MS/TP  network  in  all  devices  to  the  controller’s  highest  MAC
address used on the MS/TP trunk.

There  is  another  controller  with  the  same  MAC
Address on the BACnet MS/TP data bus

Each controller on a BACnet MS/TP data bus must have a unique MAC Address. Look at the MAC Address DIP switch on
the faceplate or under the cover of the controller. If it is set to 0 (all off), use an Allure EC-Smart-Vue sensor to check the
MAC Address.

There is another controller with the same Device
ID on the BACnet intranetwork

Each controller on a BACnet intranetwork (the entire BACnet BAS network) must have a unique Device ID. Use an Allure
EC-Smart-Vue sensor to check the Device ID of each controller.

Controller communicates well over a short network, but does not communicate on large network

Network length

Check that the total wire length does not exceed the specifications of the 

Network Guide.

Wire type

Check that the wire type agrees with the specification of the 

Network Guide.

Network wiring problem

Double check that the wire connections are correct.

Absent or incorrect network termination

Check the network termination(s). Incorrect or broken termination(s) will make the communication integrity dependent upon
a controller’s position on the network.

Number  of  controllers  on  network  segment
exceeded

The number of controllers on a channel should never exceed 50. Use a router or a repeater in accordance to the 

Network

Guide.

Max Master parameter

Configure  the  maximum  number  of  master  device  on  the  MS/TP  network  in  all  devices  to  the  controller’s  highest  MAC
address used on the MS/TP trunk.

There  is  another  controller  with  the  same  MAC
Address on the BACnet MS/TP data bus

Each controller on a BACnet MS/TP data bus must have a unique MAC Address. Look at the MAC Address DIP switch on
the faceplate or under the cover of the controller. If it is set to 0 (all off), use an Allure EC-Smart-Vue sensor to check the
MAC Address.

There is another controller with the same Device
ID on the BACnet intranetwork

Each controller on a BACnet intranetwork (the entire BACnet BAS network) must have a unique Device ID. Use an Allure
EC-Smart-Vue Series Communicating Sensor to check the Device ID of each controller.

I/O Extension Module cannot communicate on the subnetwork

Absent or incorrect supply voltage

1. Check power supply voltage between 24VAC ±15% and 24VCOM pins and ensure that it is within acceptable limits.

2. Check for tripped fuse or circuit breaker.

Overloaded power transformer

Verify that the transformer used is powerful enough to supply all controllers. See 

Power Wiring.

Network not wired properly

Double check that the wire connections are correct.

There is another controller with the same Subnet
ID on the subnetwork

Each  I/O  Extension  Module  on  the  subnetwork  must  have  a  unique  Subnet  ID.  Look  at  the  Subnet  ID  DIP  switch  on  the
faceplate of each I/O Extension Module.

Network length

Check that the total wire length does not exceed the specifications in the 

Network Guide.

Wire type

Check that the wire type agrees with the specification of the 

Network Guide.

Absent or incorrect network termination

Check the network termination(s). Only the last ECx-400 I/O Extension Module must have its EOL termination set to ON.
When  one  or  more  Allure  EC-Smart-Vue  sensors  are  connected  to  the  controller,  only  the  last  sensor  must  have  its  EOL
termination set to ON. See the 

Network Guidefor more information.

Hardware input is not reading the correct value

Input wiring problem

Check that the wiring is correct according to this manual and according to the peripheral device’s manufacturer.

Configuration problem

Using EC-gfxProgram, check the configuration of the input. Refer to the EC-gfxProgram user guide for more information.

Over-voltage or over-current at an input

An  over-voltage  or  over-current  at  one  input  can  affect  the  reading  of  other  inputs.  Respect  the  allowed  voltage  /  current
range limits of all inputs. Consult the appropriate datasheet for the input range limits of this controller.

Open circuit or short circuit

Using  a  voltmeter,  check  the  voltage  on  the  input  terminal.  For  example,  for  a  digital  input,  a  short  circuit  shows
approximately 0V DC and an open circuit shows approximately 5V DC.

Hardware output is not operating correctly

Fuse has blown (Auto reset fuse)

Disconnect the power and outputs terminals. Then wait a few seconds to allow the auto-reset fuse to cool down. Check the
power supply and the output wiring. Reconnect the power.

Output wiring problem

Check that the wiring is correct according to this manual and according to the peripheral device’s manufacturer.

Configuration problem

Using EC-gfxProgram, check the configuration of the input. Refer to the EC-gfxProgram user guide for more information.

Summary of Contents for Allure ECB-400 Series

Page 1: ...tion and subsequent operation of the device pay special attention to the following recommendations It is recommended that the controller s be kept at room temperature for at least 24 hours before inst...

Page 2: ...e Hardware Installation Guide Alternating Current Direct Current General Wiring Recommendations Risk of Electric Shock Turn off power before any kind of servicing to avoid electric shock All wiring mu...

Page 3: ...3 20 Controller Dimensions Components Figure 2 Rear view of large enclosure Figure 3 Rear view of small enclosure Figure 4 Side view of large and small enclosure...

Page 4: ...orientation must be horizontal with controller s back attached to a vertical wall surface Figure 5 Permitted Mounting Positions DIN Rail Mounted Installation 1 Ensure the DIN rail is properly mounted...

Page 5: ...ted to the grounded transformer terminal as shown below This ensures that the 24V COM terminals of all devices connected to any BACnet MS TP bus in the building are at the same potential Always use a...

Page 6: ...et Port Wireless Port Universal Inputs UI 0 20 mA Enable Disable 0 20 mA Disable 0 20mA Enable Figure 9 ECB 300 Controller Jumper Locations Factory default positions BACnet MS TP Network Board BACnet...

Page 7: ...6 Table 1 Controller Input Support Sensor Input Type Input Connection Diagram Dry Contact input UIx COM To Digital Input Digital Dry Contact NO NC RTD input for example 1000 Thermistor Input for examp...

Page 8: ...ge input used with a 0 to 10VDC or 0 to 5VDC sensor powered by its own power source 0 10V Sensor UIx COM To Analog To Digital Converter Slow Pulse Internal supply 2 wire pulse meter for ECB 203 ECB 30...

Page 9: ...PWM output controlling a 12VDC relay Maximum 60 mA minimum load resistance 200 UOx From Digital Output 12VDC Relay A1 A2 UOx COM Current 0 to 20mA universal output jumper configuration For ECB 300 EC...

Page 10: ...the cable and attaching it to a solid object with a nylon tie so that a tug on the cable will not pull out the connector on the controller Subnet Wiring with the ECB 600 Series Controller ECx 400 ser...

Page 11: ...e information and requirements to implement a BACnet MS TP network It contains information about network plan ning and MAC Address numbering schemes It can be downloaded from the www distech controls...

Page 12: ...S TP Adaptor to the NET PORT au dio plug Wire a standard 3 5 mm three conductor stereo jack as shown below The BACnet MS TP Adaptor must have an electrically isolated RS 485 port Otherwise a ground pa...

Page 13: ...Press and hold the Menu button for 5 seconds to enter the password menu 10000 is shown on the display OR Screen Timeout 15 seconds 3 Press the down button to set the number to 9995 this is the defaul...

Page 14: ...ut 15 seconds 3 Use the down button to set the number to 9995 this is the default password OR Screen Timeout 15 seconds 4 Press the Menu button to submit the password Upon submitting the password the...

Page 15: ...r s BAUD rate as follows 1 Connect an Allure EC Smart Vue Series Communicating Sensor sensor to the controller with a Cat 5e patch cable Wait for the display to show the room temperature 2 Press and h...

Page 16: ...telephone socket Connecting to the Controller s Wireless Port Each controller has a wireless port in which one end of the Wireless Receiver s telephone cable plugs in Strain relief and Terminal Block...

Page 17: ...ser s authority to operate the equipment This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed...

Page 18: ...Fast Acting Electrical System Ground Data Bus Shields Twist together and Isolate with electrical tape From Previous Device To Next Device BACnet MS TP Network ECB 400 249 ohm resistor built in for in...

Page 19: ...DIP switch on the faceplate or under the cover of the controller If it is set to 0 all off use an Allure EC Smart Vue sensor to check the MAC Address There is another controller with the same Device...

Page 20: ...The device has not received a BACnet token and therefore cannot communicate on the network Verify that the controller s MAC Address is unique on the BACnet MS TP Data Bus see Device Addressing Make su...

Reviews: