background image

6 / 20

Jumper Identification and Configuration

Controllers have the following onsite configurable jumpers.

* Factory- default positions

Subnet 

Port

Wireless 

Port

BACnet MS / TP Network EOL 

Termination

EOL Off

(Disabled)*

EOL On

(Enabled)

Net Port

Figure 8:  ECB-203 Controller Jumper Locations

Net Port

* Factory default positions

BACnet MS/ TP Network Board

BACnet MS/ TP Network EOL 

Termination

EOL Off

(Disabled)

EOL On

(Enabled)

Universal Outputs (UO)

0- 10V / 0- 20 mA Select

0- 10V

0-20mA

Subnet 

Port

Wireless 

Port

Universal Inputs (UI)

0- 20 mA Enable / Disable

0- 20 mA 

Disable

0- 20mA 

Enable

Figure 9:  ECB-300 Controller Jumper Locations

*  Factory- default positions

BACnet MS / TP Network Board

BACnet MS / TP Network

EOL Termination

EOL Off

(Disabled)*

EOL On

(Enabled)

Universal Outputs (UO)
0- 10 V / 0 - 20 mA Select

0-10V*

0- 20mA

Universal Inputs  ( UI)

0 - 20 mA Enable / Disable

0- 20 mA 

Disable*

0-20 mA 

Enable

ECB - 600 ONLY:  Subnetwork 

EOL Termination

Subnet 

Port

EOL Off

(Disabled)*

EOL On

(Enabled)

EOL Off

(Disabled)*

EOL On

(Enabled)

OR

Wireless 

Port

Typical locations: 

Quantity may vary according to controller model

Net Port

Figure 10:  ECB-400 Series and ECB-600 Series Controller Jumper Locations

Summary of Contents for Allure ECB-400 Series

Page 1: ...tion and subsequent operation of the device pay special attention to the following recommendations It is recommended that the controller s be kept at room temperature for at least 24 hours before inst...

Page 2: ...e Hardware Installation Guide Alternating Current Direct Current General Wiring Recommendations Risk of Electric Shock Turn off power before any kind of servicing to avoid electric shock All wiring mu...

Page 3: ...3 20 Controller Dimensions Components Figure 2 Rear view of large enclosure Figure 3 Rear view of small enclosure Figure 4 Side view of large and small enclosure...

Page 4: ...orientation must be horizontal with controller s back attached to a vertical wall surface Figure 5 Permitted Mounting Positions DIN Rail Mounted Installation 1 Ensure the DIN rail is properly mounted...

Page 5: ...ted to the grounded transformer terminal as shown below This ensures that the 24V COM terminals of all devices connected to any BACnet MS TP bus in the building are at the same potential Always use a...

Page 6: ...et Port Wireless Port Universal Inputs UI 0 20 mA Enable Disable 0 20 mA Disable 0 20mA Enable Figure 9 ECB 300 Controller Jumper Locations Factory default positions BACnet MS TP Network Board BACnet...

Page 7: ...6 Table 1 Controller Input Support Sensor Input Type Input Connection Diagram Dry Contact input UIx COM To Digital Input Digital Dry Contact NO NC RTD input for example 1000 Thermistor Input for examp...

Page 8: ...ge input used with a 0 to 10VDC or 0 to 5VDC sensor powered by its own power source 0 10V Sensor UIx COM To Analog To Digital Converter Slow Pulse Internal supply 2 wire pulse meter for ECB 203 ECB 30...

Page 9: ...PWM output controlling a 12VDC relay Maximum 60 mA minimum load resistance 200 UOx From Digital Output 12VDC Relay A1 A2 UOx COM Current 0 to 20mA universal output jumper configuration For ECB 300 EC...

Page 10: ...the cable and attaching it to a solid object with a nylon tie so that a tug on the cable will not pull out the connector on the controller Subnet Wiring with the ECB 600 Series Controller ECx 400 ser...

Page 11: ...e information and requirements to implement a BACnet MS TP network It contains information about network plan ning and MAC Address numbering schemes It can be downloaded from the www distech controls...

Page 12: ...S TP Adaptor to the NET PORT au dio plug Wire a standard 3 5 mm three conductor stereo jack as shown below The BACnet MS TP Adaptor must have an electrically isolated RS 485 port Otherwise a ground pa...

Page 13: ...Press and hold the Menu button for 5 seconds to enter the password menu 10000 is shown on the display OR Screen Timeout 15 seconds 3 Press the down button to set the number to 9995 this is the defaul...

Page 14: ...ut 15 seconds 3 Use the down button to set the number to 9995 this is the default password OR Screen Timeout 15 seconds 4 Press the Menu button to submit the password Upon submitting the password the...

Page 15: ...r s BAUD rate as follows 1 Connect an Allure EC Smart Vue Series Communicating Sensor sensor to the controller with a Cat 5e patch cable Wait for the display to show the room temperature 2 Press and h...

Page 16: ...telephone socket Connecting to the Controller s Wireless Port Each controller has a wireless port in which one end of the Wireless Receiver s telephone cable plugs in Strain relief and Terminal Block...

Page 17: ...ser s authority to operate the equipment This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed...

Page 18: ...Fast Acting Electrical System Ground Data Bus Shields Twist together and Isolate with electrical tape From Previous Device To Next Device BACnet MS TP Network ECB 400 249 ohm resistor built in for in...

Page 19: ...DIP switch on the faceplate or under the cover of the controller If it is set to 0 all off use an Allure EC Smart Vue sensor to check the MAC Address There is another controller with the same Device...

Page 20: ...The device has not received a BACnet token and therefore cannot communicate on the network Verify that the controller s MAC Address is unique on the BACnet MS TP Data Bus see Device Addressing Make su...

Reviews: