25
TEMPCO
This value is disabled (grey) when BMS Lithium Batt is
enabled.
Use Batt V Charged
Disable
Use Batt % Charged
Enable
No Battery
Disable
BMS Lithium Batt
Enable and set to 00 value
2
Activate Battery
Enable
1
The recommended value for Max A Charge is 75% of the rated maximum charge
current for the battery.
2
Setting the BMS Lithium Batt parameter to Enable confirms closed-loop operation.
Ensure that a checkmark and 00 (CANBus Battery mode) is displayed.
The values and parameters used are for an operating temperature of 25 deg C.
6.3.2 Closed-Loop - Batt Setup > Charge
Touch the CHARGE tab onscreen to start the programming sequence (Figure 13).
• Touch the OK button to save all onscreen values - Ignore data displayed
in GREY boxes.
Batt Setup
StartV
Batt Charge Discharge Smart Load
Float V
Start%
A
Gen Charge
Gen Force
Generator Exercise Cycle Day & Time>>
Grid Charge
CANCEL
OK
Absorbtion V
Equalization V
48.0V
48.0V
10%
10%
260 A
260 A
53.6V
55.2V
55.2V
0.0 hours
30 Days
Mon
08
:00 20min
Figure 13. Closed-Loop Battery Setup > Charge (Two 130Ah AES Batteries with 12K-P)
Batt Setup > Charge
Gen Charge
Enable if charging from a generator is desired.
1
Note: The Gen Input Breaker must be connected to the
output of an AC generator for this work.
Grid Charge
Enable if charging from the grid is desired.
2
Note: The Grid Input Breaker must be connected to
input from the grid for this to work.
StartV
Unavailable (Grey) in a closed-loop configuration.
Start%
Set to user preference based on battery State-of-charge
as a percentage. The recommended minimum is 10%.