27
Batt Setup > Discharge
Shutdown
Set to user preference based on battery State-of-charge as a
percentage. The recommended minimum is 10 %
1
Low Batt
Set to user preference based on battery State-of-charge as a
percentage. The recommended minimum is 20 %
1
Restart
Set to user preference based on battery State-of-charge as a
percentage.
1
Batt Empty V
48 V
Batt Resistance
Set to: Ten mOhm divided by the number of batteries (plus
mOhm value for cable resistance, if known).
2
Batt Charge Efficiency 98.0 %
BMS_Err_Stop
Enable (Recommended)
3
1
A closed-loop configuration uses % state-of-charge. Discharge voltage values are not
available.
2
This value should include cable and connection resistance. The formula provided is
to assist with the calculation of a general value.
3
BMS_Err_Stop MUST be enabled to cause the inverter to stop operating if there
is a communication error. If BMS_Err_Stop is disabled, the inverter will continue to
operate using the last communicated battery values.
The values and parameters used are for an assumed operating temperature of 25 deg C.
6.3.4 Batt Setup > Smart Load
Optional functionality. See Sol-Ark documentation for details on use and setup.