24
Batt Setup
Batt
Batt Capacity
Use Batt V Charged
Charge Discharge Smart Load
Use Batt % Charged
No Battery
BMS Lithium Batt
Activate Battery
Max A Charge
Max A Discharge
TEMPCO
CANCEL
OK
260 Ah
185 A
185 A
-0mV/C/Cell
00
Figure 12. Closed-Loop Battery Setup > Battery (Two 130Ah AES Batteries with 12K-P)
Batt Setup > Batt
Batt Capacity
Set to the number of Discover Lithium batteries x Ah capacity
of each. (eg. Set to 260 Ah for two AES batteries, each rated
130 Ah capacity).
Max A Charge
For a single inverter: set to the lesser of the inverter’s
max charge capacity, or the quantity of attached batteries,
multiplied by the battery model’s specific max charge rating.
For example, a 12K-P inverter would be set to the lessor of the
inverter’s max charge rate of 185 A, or 260 A for two AES 42-
48-6650 batteries rated at 130 A max charge each.
1
For a three-phase system: set to the lessor of the max charge
value for the master inverter, or the quantity of attached
batteries, multiplied by the battery model’s max charge rating,
divided by the number of inverters. For example, the 12k-P
master would be set to the lessor of the inverter’s max charge
rate of 185A, or 173 A for four AES 42-48-6650 batteries rated
at 130 A max charge each (520 A divided by three inverters).
Max A Discharge
For a single inverter: set to the lesser of the inverter’s max
discharge capacity, or the quantity of attached batteries,
multiplied by the battery model’s specific max discharge
rating. For example, a 12k-P inverter would be set to the lessor
of the inverter’s max discharge rate of 185 A, or 260 A for two
AES 42-48-6650 batteries rated at 130 A max charge each.
1
For a three-phase system: set to the lessor of the max
discharge value for the master inverter, or the quantity of
attached batteries, multiplied by the battery model’s max
charge rating, divided by the number of inverters. For
example, the master 12k-P would be set to the lessor of the
inverter’s max charge rate of 185 A, or 173 A for a battery bank
of four AES 42-48-6650 batteries rated at 130A Max Charge
each (520 A divided by three inverters).