20
Batt Setup
StartV
Batt Charge Discharge Smart Load
Float V
Start%
A
Gen Charge
Gen Force
Generator Exercise Cycle Day & Time>>
Grid Charge
CANCEL
OK
Absorbtion V
Equalization V
48.0V
48.0V
10%
10%
185 A
185 A
53.6V
55.2V
55.2V
0.0 hours
30 Days
Mon
08
:00 20min
Figure 10. Open-Loop Battery Setup > Charge (Two 130Ah AES Batteries with 12K-P)
Batt Setup > Charge
Gen Charge
Enable if charging from a generator is desired.
1
Note: The Gen Input Breaker must be connected to the output
of an AC generator for this work.
Grid Charge
Enable if charging from the grid is desired.
2
Note: The Grid Input Breaker must be connected to input from
the grid for this to work.
StartV
Set the value to the desired battery voltage that will trigger
battery charging. The absolute minimum is 48 V.
Start%
Unavailable (Grey) in an open-loop configuration.
A
Set to the same Amp value that was used for Max A Charge.
3
Float V
Set to 53.6 V
Absorption V
Set to 55.2 V
4
Equalization V
55.2 V
5
30 days
0.0 hours
5
Gen Exercise Cycle
Day & Cycle
Refer to Solar-Ark documentation.
Gen Force
Refer to Solar-Ark documentation.
1
Left column options are for Gen Charge AutoStart values (Reference Sol-Ark
documentation for more details on the generator AutoStart function.
2
Right Column options are for Grid Charge values.
3
If need be, this value is used to curtail the maximum current output of the charger.
4
Absorption will stop at 2% of the set capacity of the battery bank and move to the
float value.
5
Lithium batteries MUST not be equalized. Using a value of 55.2 for Equalization V
and zero for Hours ensures that the batteries will not be equalized.
The values and parameters used are for an operating temperature of 25 deg C.