background image

1

805-0038 REV A

(950-0025)

SOL-ARK USER 

MANUAL

Summary of Contents for 950-0025

Page 1: ...1 805 0038 REV A 950 0025 SOL ARK USER MANUAL...

Page 2: ...cy Inverter Charger PIN Assignments 11 5 0 Installing and Connecting LYNK II to the Sol Ark Network 12 5 1 Networking Discover Lithium Batteries with LYNK II 12 5 2 Connecting LYNK II to the Sol Ark N...

Page 3: ...ing and configuring batteries Installing and configuring systems activated by relays 1 2 Warning Caution Notice and Note Messages Messages in this manual are formatted according to this structure WARN...

Page 4: ...r electronics read all instructions and cautionary markings on all components and appropriate sections of their manuals Use personal protective equipment when working with batteries Do not dispose of...

Page 5: ...r rings watches bracelets or necklaces 2 0 Documentation This Application Note provides information about the integration of LYNK and AEbus network enabled Discover Lithium Batteries using the LYNK II...

Page 6: ...arging process LYNK II also enables the remote monitoring of Discover Lithium battery SoC and data logging of multiple sites using the data monitoring services offered by off grid inverter systems Dis...

Page 7: ...2 Compatibility LYNK II Communication Gateway is compatible with the following Discover Lithium Batteries AES LiFePO4 44 24 2800 44 48 3000 42 48 6650 HELIOS ESS 46 24 1560 46 48 1540 Sol Ark Outdoor...

Page 8: ...urgeValue Inverter Efficiency 48V Low Battery Cut Off Model Inverter Peak Charger Continous Max3 42 48 6650 Minimum per inverter4 44 48 3000 Minimum per inverter5 46 48 1540 Minimum per inverter6 Sol...

Page 9: ...d with jumpers Detailed PIN configurations are included in the LYNK II User Manual but are repeated here for convenience NOTE LYNK II terminates the AEbus and LYNK Network by default Do not remove the...

Page 10: ...3 4 1 2 2 1 2 1 2 5 6 5 6 5 6 5 9 10 9 10 9 10 LOW HIGH GROUND 9 10 7 8 6 3 1 Figure 2 Sol Ark Outdoor CAN Pin Assignment 4 2 1 Sol Ark Outdoor Inverter Charger PIN Assignments 5K P 8K P 12K P 15K P...

Page 11: ...1 2 2 1 2 1 2 5 6 5 6 5 6 5 9 10 9 10 9 10 LOW HIGH GROUND 9 10 7 8 6 3 1 Figure 3 Sol Ark Indoor Legacy CAN Pin Assignment 4 2 2 Sol Ark Indoor Legacy Inverter Charger PIN Assignments 8K Hybrid 12K H...

Page 12: ...work Refer to the LYNK II Communication Gateway User Manual 850 0033 for detailed instructions on network layouts connections and terminations for compatible Discover Lithium battery models Some key r...

Page 13: ...terminated When using LYNK II with an AEbus network ensure that a terminator is installed at the end opposite LYNK II Figure 5 Helios LYNK II and HELIOS ESS batteries are both internally terminated W...

Page 14: ...ion cable into the LYNK II CAN out port and the other end into the correct CAN port of the Sol Ark inverter charger NOTE Ensure that all Sol Ark inverters are using COMM firmware version 1 4 3 0 or hi...

Page 15: ...t Gen In 50A 50A 50A PV Input DC Input Batt Disconnect Neutral Ground L1 L2 L1 L2 CAN RS485 SOL ARK BUS Figure 7 Indoor Sol Ark 12K Hybrid Legacy PV1 PV1 PV2 PV2 PV Input DC Input CAN SOL ARK BUS Figu...

Page 16: ...l need to be manually converted to an open loop configuration to resume operation Therefore as a precautionary measure it is recommended to program the Sol Ark inverter with the correct voltage based...

Page 17: ...inverter to ON 2 Using the touch screen and keypad on the inverter navigate from the SYSTEM SETUP menu to the BATT SETUP menu screen 3 Enable and disable parameters according to the instructions in th...

Page 18: ...es x Ah capacity of each For example set to 260 Ah 2 x 130 Ah for two AES 42 48 6650 batteries Max A Charge For a single inverter set to the lesser of the inverter s max charge capacity or the quantit...

Page 19: ...S 42 48 6650 batteries rated at 130A Max Charge each 520 A divided by three inverters TEMPCO Set to 0 mv C Cell 2 Use Batt V Charged Enable Use Batt Charged Disable No Battery Disable BMS Lithium Batt...

Page 20: ...he absolute minimum is 48 V Start Unavailable Grey in an open loop configuration A Set to the same Amp value that was used for Max A Charge 3 Float V Set to 53 6 V Absorption V Set to 55 2 V4 Equaliza...

Page 21: ...he number of batteries plus the mOhm value of resistance for interconnection and homerun cabling 2 Batt Charge Efficiency 98 0 1 Discharge state of charge percentage values are unavailable in an open...

Page 22: ...op parameter function is not enabled the Sol Ark inverter will continue to operate based on the last communicated battery values Depending on the mode of operation at the time of communication fault a...

Page 23: ...to Navigate the Sol Ark onsreen menus Enable parameters Activate the adjustment of values Save all onscreen settings Values are adjusted using the keypad NOTE Enable parameters with a CHECKMARK and di...

Page 24: ...ty of attached batteries multiplied by the battery model s max charge rating divided by the number of inverters For example the 12k P master would be set to the lessor of the inverter s max charge rat...

Page 25: ...e all onscreen values Ignore data displayed in GREY boxes Batt Setup StartV Batt Charge Discharge Smart Load Float V Start A Gen Charge Gen Force Generator Exercise Cycle Day Time Grid Charge CANCEL O...

Page 26: ...entation for more details on the generator AutoStart function 2 Right Column options are for Grid Charge values 3 If need be this value is used to curtail the maximum current output of the charger The...

Page 27: ...ficiency 98 0 BMS_Err_Stop Enable Recommended 3 1 A closed loop configuration uses state of charge Discharge voltage values are not available 2 This value should include cable and connection resistanc...

Page 28: ...28 NOTES...