Product Information
Safety technics modular generation in metal housing version 08 dated: 2009-04-10 page 12 from 32
Selection of the monitoring frequencies via the DIP switch S3 for the tool setting and semi automatic mode
R and SH Table:
SH- or R1-input is connected to 24V,F-Inputs are disconnected.
SH
R1
SH
R1
Hz
Hz
S3
Hz
Hz
S3
00
50
125
1 & 2 off
00
50
125
1 & 2 off
01
240
600
1 & 2 on
01
96
600
1 & 2 on
External wiring for the automatic function mode via D- and F-terminal
Selection of the monitoring frequencies for the automatic function mode
D-Table:
F1-F4 connected to 24V
F-Table:
D-Wiring 0 to 15
D-Inputs connected to 24V
F-Inputs connected to 24V
24V
D1
D2
D3
D4
Hz
24V
F1
F2
F3
F4
%
00
100
00
5Hz
01
150
01
25
02
200
02
30
03
275
03
35
04
355
04
40
05
400
05
45
06
450
06
50
07
500
07
55
08
550
08
60
09
630
09
65
10
700
10
70
11
800
11
75
12
900
12
80
13
1000
13
85
14
1100
14
90
15
1250
15
100
The frequency values in Adjusting table are calculated as follows:
Table value = Encoder frequency (adjusted divisor at S1 and S2) + 1
Using the modules to monitor the function modes of a machine
Using the inputs D- and F-inputs to monitor the automatic function mode (mode 1)
With the D-inputs or S5 DIP-switch 16 different monitoring frequencies (100-1250Hz) for mode 1 can be selected.
See D-Table. Every value of the 16 frequencies can be decreased from 100 to 25% via the F-inputs or S6 DIP-
switch. See F-Table.
Mode 1 will be monitored, if one or more F-inputs are connected to 24V. All F-inputs have to be disconnected from
24V, if other function modes have to be monitored. See F-Table
Using the R1-input to monitor the semi automatic function mode (mode 3)
Mode 3 can be monitored, if the R1-input is connected to 24V. For the monitoring of mode 3 the F-inputs have to
be disconnected from 24V.
Using the SH-input to monitor the tool setting function mode (mode 2)
Mode 2 can be monitored, if the SH-input is connected to 24V. For the monitoring of mode 2 the F-inputs and the
R1-input have to be disconnected from 24V.
For the monitoring of the tool setting and the semi automatic function mode there are 2 monitoring frequencies.
These can be selected via the DIP-switch S3. See R1 and SH Table.
Monitoring of the standstill
To monitor the standstill the inputs F1-F4, R1- and SH-input have to be disconnected from 24V.
STOP output of the output modules
The STOP output of all output modules is independent of all function modes. It works autarkic.
Priority of the inputs: F > R1
R1 > SH
SH > Standstill