EVO Control Panel
11
4.4.8 24Hr Gas Zones*
SECTION
[0400]: F
IRST
DIGIT
= 8
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 8
When a 24Hr Gas zone opens, the control panel will immediately generate
an alarm.
4.4.9 24Hr Heat Zones**
SECTION
[0400]: F
IRST
DIGIT
= 9
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= 9
When a 24Hr Heat zone opens, the control panel will immediately generate
an alarm.
** UL Note:
UL Listed compatible devices must be used for UL systems. For
UL Listed systems, this type of zone should be programmed as a pulsing Fire
alarm.
4.4.10 24Hr Water Zones*
SECTION
[0400]: F
IRST
DIGIT
= A
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= A
When a 24Hr Water zone opens, the control panel will immediately
generate an alarm.
4.4.11 24Hr Freeze Zones*
SECTION
[0400]: F
IRST
DIGIT
= B
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= B
When a 24Hr Freeze zone opens, the control panel will immediately
generate an alarm.
* UL Note:
UL Listed compatible devices must be used for UL systems. For UL
Listed systems, this type of zone must be programmed as a silent auxiliary
alarm.
4.4.12 Delayed 24Hr Fire Zone
(Not to be used with UL Listed systems)
SECTION
[0400]: F
IRST
DIGIT
= C
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= C
The Delayed 24Hr Fire Zone definition from
on page 12 is used in
homes where a smoke detector often generates false alarms. A zone
programmed as Fire becomes normally open and requires an EOL resistor.
The keypads must be assigned to the same partition as the Delayed 24Hr Fire zone
for the buzzer to activate.
* UL Warning: For UL/ULC installations, a Fire zone cannot be bypassed and its
alarm type must be Pulsed (audible).
4.4.13 Standard 24Hr Fire Zone
SECTION
[0400]: F
IRST
DIGIT
= D
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= D
A zone programmed as Fire becomes normally open and requires an EOL
resistor. When a Standard 24Hr Fire Zone triggers, the control panel can:
• send a Zone Alarm report code (see
• send a Fire Loop Trouble Report (see
tamper/wiring fault occurs on a Fire Zone. A “Zone Fault Trouble” will
also appear in the keypad's Trouble Display.
• generate a Fire alarm, which can be silent, pulsed, steady or report only.
Fire alarms generate an intermittent signal (see
* UL Warning: For UL/ULC installations, a Fire Zone cannot be bypassed
and its alarm type must be Pulsed (audible).
Figure 13: Bell/Siren Output During Fire Alarm
4.4.14 Stay Delay Zone
SECTION
[0400]: F
IRST
DIGIT
= E
AND
F
S
ECTIONS
[0101]
TO
[0196]: F
IRST
DIGIT
= E
AND
F
Using the Regular or Force arming methods, the control panel processes
the zone as an Instant zone (see
on page 10). Using the Stay
or Instant arming methods and the zone is triggered, the control panel will
not generate an alarm until the programmed Stay Delay elapses. A zone
defined as Stay Delay 1 follows the Entry Delay 1 Timer of its assigned
partition. A zone defined as Stay Delay 2 follows the Entry Delay 2. To
program the Entry Delay Timers, refer to
4.5 Zone Partition Assignment
SECTION
[0400]: S
ECOND
DIGIT
= 1
TO
8
S
ECTIONS
[0101]
TO
[0196]: S
ECOND
DIGIT
= 1
TO
8
Assign zones to one partition.
4.6 Zone Options
The zone options from are described below. Refer to the EVO programming
guide for additional information on Zone Programming.
4.6.1 Auto Zone Shutdown
SECTION
[0400]: O
PTION
[1]
S
ECTIONS
[0101]
TO
[0196]: O
PTION
[1]
(default =
000
) When enabled, the control panel will stop generating alarms
once the Auto Zone Shutdown Limit is reached. It resets every time the
partition that is assigned to the corresponding zone is armed. To program
the Auto Zone Shutdown Limit, enter the desired 3-digit counter (000 to
015) into section corresponding to the desired partition (000 = disabled):
4.6.2 Bypass Zones
SECTION
[0400]: O
PTION
[2]
S
ECTIONS
[0101]
TO
[0196]: O
PTION
[2]
(default =
enabled
) Allow zones to be Manually Bypassed.
4.6.3 Stay Zones
SECTION
[0400]: O
PTION
[3]
S
ECTIONS
[0101]
TO
[0196]: O
PTION
[3]
Only zones with option
[3]
enabled will be bypassed when the partition is
Stay armed or Instant armed. All other zones will remain activated. Fire
Zones cannot be set as Stay Zones.
4.6.4 Force Zones
(Not to be used with UL Listed systems)
SECTION
[0400]: O
PTION
[4]
S
ECTIONS
[0101]
TO
[0196]: O
PTION
[4]
Only zones with option
[4]
enabled can be bypassed when the partition is
Force armed. Fire Zones cannot be Force Zones.
Partition 1:
[3114]
Partition 5:
[3514]
Partition 2:
[3214]
Partition 6:
[3614]
Partition 3:
[3314]
Partition 7:
[3714]
Partition 4:
[3414]
Partition 8:
[3814]