20
Reference & Installation Manual
8.5.1 Tamper Bypass Options
S
ECTION
[3034]: O
PTION
[7]
(default =
enabled
) When enabled in section
[3034]
, the control panel will
ignore the zone’s bypass definition and will follow the option set in
(page 19) if a tamper or wire fault occurs on a bypassed zone. When
disabled, Tamper Recognition follows the zone’s bypass definition. This
means that the control panel will not perform any action if a tamper or wire
fault occurs on a bypassed zone.
8.6 Keypad Panic Options
(default =
disabled
) The control panel can generate an alarm (audible, fire
or report only) by pressing the keypad Panic key(s). Refer to the table
below for the keypad Panic keys. In the section that corresponds to the
desired partition, enable or disable options
[1]
through
[6]
:
Report Only
The keypad emits a single confirmation beep and transmits the report code.
Audible Alarm
The control panel activates the
BELL
output until a user cancels the alarm or
when the Bell Cut-Off Timer elapses .
Fire Alarm
Same as audible operation, except that the bell/siren output will be pulsed.
* UL Note:
For UL Listed systems, all emergency non-medical and auxiliary
panic alarms will be report only.
Partition 1:
[3123]
Partition 3:
[3323]
Partition 5:
[3523]
Partition 7:
[3723]
Partition 2:
[3223]
Partition 4:
[3423]
Partition 6:
[3623]
Partition 8:
[3823]
Option Feature
Press and Hold 2 Seconds:
[1]
Panic 1
*
LCD keypads:
Keys
[1]
and
[3]
simultaneously
Grafica keypads:
The
key
[2]
Panic 2
*
LCD keypads:
Keys
[4]
and
[6]
simultaneously
Grafica keypads:
The
key
[3]
Panic 3
LCD keypads:
Keys
[7]
and
[9]
simultaneously
Grafica keypads:
The
key
Option Alarm Type
[4]
Panic 1:
*
ON
= Audible
OFF
= Report Only
[5]
Panic 2:
*
ON
= Audible
OFF
= Report Only
[6]
Panic 3:
ON
= Fire
OFF
= Report Only