19
Figure 14
- WEB PATH FOR METER CALIBRATION
f) Attach the weight to the free end of the rope as shown above. Adjust the CAL A pot. as required to
set the meter needle at the value of the weight.
g) Remove the weight and observe the tension meter. If the needle is not on 0, adjust the ZERO A
pot. as needed. Repeat step f.
h) Repeat steps f and g if needed.
TENSION METER CALIBRATION IS COMPLETED.
NOTE:
The ZERO B and CAL B pots. are only used with the Dual Calibration (DC) option.