Changing parameters menu
FREQUENCY DRAIN EVE-
RY XX CYCLES
Possible value : between 1 and 5
If anti-foam enabled, so value betw een 1 and 200 min.
CYCLIC DRAIN PERIOD
X.X SEC
Possible value : between 0.5 and 20 sec
This allow s to adjust the time of short drains after a succession
of w ater intakes. If some foam is noticed inside the w ater tank
(w hen using softened w aters), this draining time should be
increased .
STOP RTH WHEN
M AINTENANCE : YES
COOLING TANK :
YES
M ODBUS ADDRESS
XX
TRANSM ISSION SPEED
9600 b/s
DRAINING AFTER
SHUT DOWN ? YES
Possible value : between 1 and 32
This allow s to input an indentification number w hen
there is a number of humidifiers on the bus line.
Possible value : 1200, 2400, 4800 and 9600 b/s
This allow s to synchronise the communication speed
betw een the RTH and the trans mission system.
Possible value : YES or NO
Possible value : YES or NO
Possible value : between 1 AND 168 H
DRAINING AFTER STOP
OF XXX H
If end of period draining
has been enabled
HOM E M ENU
IMPORTANT NOTICE
The units have a factory default maintenance time of 300 hours that suits to most cases. The exact maintenance frequency is
variable and depends on the water quality, the hours of run and the lev el of demand for humidif ication. New installations should be
inspected or serv iced f requently to enable a suitable maintenance routine to be established.
Possible value : YES or NO
This enables or not a cooling cycle of the w ater tank
before servicing