Pictures for illustrati ng pur poses o nly
27
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Power
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating element
(KW)
7
7
460
3
7
6
1
3
1.9 (277V)
15
16
460
3
15
12
1
3
4.3 (277V)
20
23
460
3
22
18
1
6
3 x 1.9 (277V)
30
32
460
3
30
24
1
6
4.3 (277V)
40
39
460
3
37
29
1
9
6 x 4.3 (277V)
3 x 1.9 (277V)
50
47
460
3
45
36
1
9
4.3 (277V)
60
54
460
3
52
41
2
12
9 x 4.3 (277V)
3 x 1.9 (277V)
70
63
460
3
60
48
2
12
4.3 (277V)
80
77
460
3
73
58
2
18
12 x 4.3 (277V)
6 x 1.9 (277V)
90
86
460
3
82
65
2
18
15 x 4.3 (277V)
3 x 1.9 (277V)
100
95
460
3
90
72
2
18
4.3 (277V)
RTH steam humidifier in 3 x 460V - 50/60Hz
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Power
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating element
(KW)
7
8
480
3
7
6
1
3
1.9 (277V)
15
17
480
3
16
14
1
3
4.3 (277V)
20
25
480
3
23
19
1
6
3 x 1.9 (277V)
30
35
480
3
31
26
1
6
4.3 (277V)
40
42
480
3
38
32
1
9
6 x 4.3 (277V)
3 x 1.9 (277V)
50
52
480
3
47
39
1
9
4.3 (277V)
60
59
480
3
54
45
2
12
9 x 4.3 (277V)
3 x 1.9 (277V)
70
69
480
3
63
52
2
12
4.3 (277V)
80
84
480
3
76
63
2
18
12 x 4.3 (277V)
6 x 1.9 (277V)
90
94
480
3
85
71
2
18
15 x 4.3 (277V)
3 x 1.9 (277V)
100
103
480
3
94
78
2
18
4.3 (277V)
RTH steam humidifier in 3 x 480V - 50/60Hz
Beware ! Before connecting power, make sure that the electrical installation has been made
according to the above-mentioned values.
ALL WORKS CONCERNED WITH THE ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY SKILLED AND QUALIFIED PERSONNEL.
E
LECTRO
V
AP
RTH-V2
Electrical table