Three ventilation packs permit the use of the humidifier in direct in-space applications
where there is no ductworks.
The Blower Packs BP1 & BP2 can be set on the top of the RTH 5 to 30 while a wall set-
ting is required f or the models ranging up. The EHF III blower pack also requires to be
wall installed. The distance between the humidifier and the v entilation pack(s) should not
exceed 3m.
For use with RTH 60, two BP2 should be installed while two EHF III must be used in
combination with RTH 70 to 100, equally distant (X). (X1=X2).
A Ø40/60 mm reductor union must be used for connecting the BP1 or BP2 to the humidi-
fier while a Ø 40/50 mm reductor must be used f or connecting the EHF III to the humidi-
fier
Allow a 3 m. distance ahead to the v entilation pack f or a f ree diffusion of steam.
The electrical connection of the ventilation packs to the humidif ier is via terminal block 3
& 4 on the DIN rail.
For use and installation of the Blower Pack ventilation units, please refer to the Blower
Pack technical manual av ailable in English.
As far as the EHF-3 is concerned, please revert to the recommendations given on
the EHF-3 information sheet. Never connect the EHF-3 unit on the terminals 3 & 4
of the humidifier when a 100VA transformer is installed inside the ElectroVap RTH
humidifier.
Width
Heigth
Depth
Weight
Kg
dB
Kg/h maxi
out put
m3/ h
Connecting Ø
Compatible
with
BP1
260mm
170mm
285mm
2
40
5
53
Ø 25 mm
RTH 5
BP2
260mm
170mm
285mm
2.6
40
30
320
Ø 40 mm
RTH 15-20-30
EHF3
495mm
356mm
406mm
15
48
55
780
Ø 50 mm
RTH 40 to 50
E
LECTRO
V
AP
RTH-V2
Room ventilation packs
0,50m mini
1m mini
Dimensions & characteritics
BP1 & BP2
Examples of installation
EHF-3
TAKE CARE :
Attach hose on wall bef ore connecting
it to Blower Pack.
1
5
°
1
5
°
1
1
X1
X2
Equilibrage d u résea u
vapeu r X, soit X1 =X2
Stea m distrib utio n Y u nion
Ø 6 0 m m
-
2 x Ø 4 0 m m
(code: DI V0 01 9)
Steam hoses should be
equally distant — X1=X2