Implemented protocols in UNIGATE® CM
14.3.1.11 Slave mode
The Slave mode can be activated through WINGATE
®
. In case the Slave mode is enabled, then
only the starting sequence of the master function is not transferred. It is not a CANopen
®
Slave
conforming to the standards and an EDS file is not supplied.
14.3.1.12 CAN Baud rate and address
The CAN baud rate and Node-ID (only in Slave mode) can be set via WINGATE.
14.3.1.13 PROFIBUS Ident Nr. (Gerätetausch V2862)
The Ident Number is = 3218h. If you want to replace a UNIGATE CM device in an existing project
with a V2862 UNIGATE
®
CO (M)-ProfibusDP, you can change back the Ident Number to the old
Version 2862h via this parameter. As a result you can keep the old GSD file and you don’t have
to change the project.
Note: The configuration file (*.gwc) of the UNIGATE
®
CO (M)-ProfibusDP cannot be loaded in the
UNIGATE
®
CM.
There may be differences in the temporal data exchange.