PROFIBUS DP
Deutschmann Automation GmbH & Co. KG
36
UNIGATE
®
Feldbus-Gateway UNIGATE
®
CM - PROFIBUS V. 1.6
23.6.17
The diagnostic information of a DP Slave consists of standard diagnostic information items
(6 bytes) and a user-specific diagnostic information item. (Error number)
Telegram for diagnostic request:
Diag.station does not exist (sets Master)
Diag.station not_ready: Slave is not ready for
data exchange
Diag.cfg_Fault
Configuration data does not correspond
Diag.ext_diag
Slave has external diagnostic data
Diag.not supported: Requested function is not
supported in the Slave
Diag.invalid_slave_response (sets Slave
permanently to 0).
Diag.prm_fault
Incorrect programming (identification number etc.)
Diag.master_lock (sets Master)
Slave has been programmed by another Master
Octet 10
Diag.Prm_req
Slave must be reprogrammed
Diag.Stat_diag
Static diagnostic (byte Diag-Bits)
Permanently set to 1
Diag.WD_ON
Response monitoring active
Diag.freeze_mode
Freeze command received
Sync_mode
Sync command received
reserved
Diag.deactivated (sets Master)
Octet 20