Technical data
Deutschmann Automation GmbH & Co. KG
54
UNIGATE
®
Feldbus-Gateway UNIGATE
®
CM - PROFIBUS V. 1.6
23.6.17
15.1.1 Interface data
The table below lists the technical data of the interfaces and ports on the device. The data has
been taken from the corresponding Standards.
Interface designation ProfibusDP
RS232-C
RS485/RS422
CANopen
®
No. Physical interface
RS485
RS232-C
RS485/RS422
RS485
1
Standard
EIA Standard
DIN 66020
EIA Standard
CiA
®
DS 102
2
Transmission mode
Symmetrical
asynchronous
serial
half-duplex
Difference signal
Asymmetrical
asynchronous
serial
full duplex
Level
Symmetrical
asynchronous
serial
half-duplex
full duplex at RS422
Difference signal
Symmetrical
asynchronous
serial
half-duplex
Difference
signal
3
Transmission method
Master / Slave
Master / Slave Master / Slave
Master / slave
4
Number of users :
- Transmitters
- Receivers
32
32
1
1
32
32
32
32
5
Cable length:
- Maximum
- Baud rate-dependent
1200 m
93.75 kBd
1200
m
187.5 kBd
1000
m
500 kBd
400 m
1.5 MBd
200 m
1.5 MBd
100 m
15 m
no
1200 m
93.75 kBd
1200
m
312, kBd
500 m
625 kBd
250 m
1300 m
50 kBd
1300 m
100 kBd
640 m
200 kBd
310 m
500 kBd
112 m
1 MBd
40 m
6
Bus topology
Line
Point-to-point Line
Line
7
Data rate:
- Maximum
- Standard values
12 Mbit/s
9.6 kBit/s
19.2 kBit/s
93.75 kBit/s
187.5 kBit/s
500 kBit/s
1.5 Mbit/s
3 MBit/s
6 MBit/s
12 Mbit/s
120 kBit/s
2.4 k/B
4.8 k/B
9.6 kBit/s
19.2 kBit/s
38.4 kBit/s
625 kBaud
2.4 kBit/s
4.8 kBit/s
9.6 kBit/s
19.2 kBit/s
57.6 kB
312.5 kB
625 kB
1Mbit/s
125 kB
250 kB
500 kB
1 MB
8
Transmitter:
- Load
- Maximum voltage
- Signal, unloaded
- Signal, loaded
54
- 7 V ... 12 V
5 V
1.5 V
3 ... 7 k
25 V
15 V
5 V
54
- 7 V ... 12 V
5 V
1.5 V
54
- 7 V ... 12 V
5 V
1.5 V
9
Receiver:
- Input resistance
- Max. input signal
- Sensitivity
12
- 7 V ... 12 V
0.2 V
3 ... 7
15 V
3 V
12
- 7 V ... 12 V
0.2 V
12
- 7 V ... 12 V
0.2 V