background image

 

19

ITEM

DESCCRIPTION

COMMENTS

PART #

1

HEAT EXCHANGER ASSEMBLY

Heat exchanger only

B01701

2

FLOOR BAFFLE

B01708

3

BOTTOM DIVIDER ASSEMBLY

Panel and 3 gaskets included

B01725

4

DD BLOWER SUPPORT 

B01724

5

BAFFLE

B01707

6

PANEL ASSEMBLY, LEFT SIDE 

Panel, insulation, baffle and filter rack included

B03197-03

7

INSULATION, LEFT SIDE PANEL

B03216-02

8

FILTER  SUPPORT

B03371-01

9A

SMOKE BOX

B01697

9B

COVER ASSEMBLY, SMOKE OUTLET

B02200

10

FLOOR ASSEMBLY

Floor, baffle and insulation included

B01812

11

INSULATION

B01526-23

12

BAFFLE ASSEMBLY

B01826-01

13

PANEL ASSEMBLY, TOP REAR

Panel and insulation included

B03374-02

14

DOOR ASSEMBLY, REAR

Door, handle and insulation included

B03202

15

DIVIDER, TOP

B01710

16

FILTER SUPPORT

B01709-01

17

PANEL ASSEMBLY, RIGHT SIDE

Panel, insulation, baffle and filter rack included

B03197-01

18

INSULATION, RIGHT SIDE PANEL

B03216-01

19

FRONT PANEL ASSEMBLY

Panel and insulation included

B01827-01

20

INSULATION, FRONT PANEL ASSEMBLY

B01722

21

TOP PANEL, ELECTRICAL COMPARTMENT

B01208

22

BURNER COMPARTMENT, RIGHT SIDE

B01716-01

23

ELECTRICAL PANEL

B01133

24

ELECTRICAL PANEL, INTERIOR

B01209

25A

ACCESS DOOR ASSEMBLY

B01384

25B

INSULATION, ACCESS DOOR

B01258-01

25C

INSULATION, ACCESS DOOR SIDE

B01259-02

25D

INSULATION, ACCESS DOOR SIDE

B01259-01

26

CORNER CONDUIT

B01220

27

BURNER COMPARTMENT, LEFT SIDE

B01716-02

28

FAN LIMIT, 11-1/2"

R02I002

29

MOTOR ASSEMBLY 1/3 HP

Motor and motor support assembly

B01890-01

30

BLOWER ASSEMBLY, REPLACEMENT

Blower, motor and capacitor

B01403-01

31

BLOWER, 100-8R DD

B03720-02

32

OBSERVATION DOOR ASSEMBLY

B02111

33

CAPACITOR, 5 MF

L01I001

34

PAPER FILTER, 12" x 20" x 1"

Z04F008

35

FLANGE NUT, HEXAGONAL 3/8-16NC BRASS

F07O001

36

GASKET, SMOKE PIPE COVER

B01214

37

THERMODISC PLATE

B01721-02

38

ROCKER SWITCH, SPST

L07F003

39

THUMBSCREW KIT ASSEMBLY

K03009

40

SINGLE TERMINAL STRIP, 6 BUSS

L05F001

41

TRANSFORMER, 120-24VAC

L01F009

42

RELAY, SPDT 24 VAC

L01H009

43

SCREW TERMINAL STRIP, 6-POSITION

A00294

44

CAPACITOR SUPPORT

B01024

45

GASKET, PEEP HOLE

B01014

46

HANDLE, RECESSED, BLACK

Z99F050

47

BUSS RETAINING CLIP

L05F007

48

SEAL STRIP, 1/4" x 1/8" x 25'

J06L002

49

ELECTRICAL KIT, BVSO EXT.

B03118-01

50

BLOCKED VENT SHUT-OFF BVSO-225

Z06G001

51A

BURNER ASSEMBLY, BECKETT AFG-F3

B00569

51B

BURNER, RIELLO 40-F3

N01F011

52

INTERIOR BVSO ELECTRIC KIT

B03377-01

Table 7: Parts list - AMT1-IM2 

 

B50054B 

Summary of Contents for AMT100B34-IM2

Page 1: ...lified service technician Printed in Canada Printed on 100 recycled paper AMT AMT S DNS 0537 Rev B AMiT AMT I Models AMT100B34 SM1 AMT100B34 IM2 AMiT AMT200B34 SM3 AMT200B34 IM2 AMiT INSTALLER SERVICE...

Page 2: ...ment and blower regulator 8 Figure 2 Model AMT1 1M2 13 Figure 3 Model AMT1 SM1 13 Figure 4 Model AMT2 IM2 14 Figure 5 Model AMT2 SM3 14 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2 15 Figure 7 Wiring...

Page 3: ...follow this caution may result in environmental pollution Remove and recycle all components or materials i e oil electrical and electronic components insulation etc before unit final disposal CAUTION...

Page 4: ...nt of the furnace Table 1 indicates the minimum ventilation opening dimensions required Table 1 Minimum ventilation openings dimensions required in a closet or enclosure Input BTU h Width Height 75 00...

Page 5: ...ly inspected This inspection should include the following a Inspection for any deterioration in the chimney or vent If deterioration is discovered the chimney must be repaired or the vent must be repl...

Page 6: ...e primary relay When installing optional accessories on this appliance follow the manufacturer s installation instructions included with the accessory Other than wiring for the thermostat wire with a...

Page 7: ...oper procedure for performing this operation is as follows a Start the appliance and from the test port near the BREACH PLATE VTK location or on the flue pipe just before the draft regulator chimney p...

Page 8: ...duct static pressure Cooling The blower speed may be adjusted in the field to deliver the required airflow for cooling as outlined in Table 5 according to the selected model Constant Blower Switch Th...

Page 9: ...burner from the furnace 5 Clean the secondary tubes and the primary cylinder with a stiff brush and remove debris with a vacuum cleaner 6 Before reassembling the furnace the heat exchanger and combust...

Page 10: ...e telephone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lb psi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross flue temperature F Am...

Page 11: ...tage range Rated current Amps Minimum ampacity for w iring sizing Max w ire lenght Max fuse size Amps Control transformer External control pow er available Heating Cooling BLOWER DATA Blow er speed at...

Page 12: ...FURNACE 20 32 cm 8 0 6 m 24 APPLICATION SIDES TOP FLUEPIPE EXTERNAL STATIC PRESSUREWITH AIR FILTER 0 2 W C 0 3 W C 0 4 W C 0 5 W C HIGH 1425 1350 1305 1250 MED HIGH 1130 1045 1000 950 MED LOW 840 810...

Page 13: ...13 Figure 2 Model AMT1 IM2 Figure 3 Model AMT1 SM1...

Page 14: ...14 Figure 4 Model AMT2 IM2 Figure 5 Model AMT2 SM3...

Page 15: ...15 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2...

Page 16: ...16 Figure 7 Wiring diagram AMT1 SM1 and AMT2 SM3 heating only...

Page 17: ...17 Figure 8 Wiring diagram MT1 SM1 and AMT2 SM3 heating and optional cooling...

Page 18: ...18 Figure 9 Parts list AMT1 IM2 B50054B...

Page 19: ...EL B01133 24 ELECTRICAL PANEL INTERIOR B01209 25A ACCESS DOOR ASSEMBLY B01384 25B INSULATION ACCESS DOOR B01258 01 25C INSULATION ACCESS DOOR SIDE B01259 02 25D INSULATION ACCESS DOOR SIDE B01259 01 2...

Page 20: ...20 Figure 10 Parts list AMT1 SM1 B50055B...

Page 21: ...3 01 19 FRO NTPA NELA SSEM BLY B01827 01 20 INSULA TIO N FRO NTPA NEL B01722 21 THERM O DISCPLA TE B01843 22 O BSERV A TIO NDO O RA SSEM BLY B02111 23 CO RNERCO NDUIT B01818 24 CO M PA RTM ENTCO V ER...

Page 22: ...22 Figure 11 Parts list AMT2 SM3 B50056B...

Page 23: ...ONT PANEL B01767 19 ELECTRICAL WIRING RACEWAY B01830 20 WIRE CHANNEL B01763 21 FLOOR ASSEMBLY B01769 22A MOTOR ASSEMBLY1 3 HP Motor and motor support assembly B01890 01 22B BELLYBAND ASSEMBLY B01888 2...

Page 24: ...24 Figure 12 Parts list AMT2 IM2 B50057C...

Page 25: ...3B INSULATION ACCESS DOOR B01258 01 23C INSULATION ACCESS DOOR SIDE B01259 02 23D INSULATION ACCESS DOOR SIDE B01259 01 24 CORNER CONDUIT B01220 25 BURNER COMPARTMENT LEFT SIDE B01716 02 26 WIRE CHANN...

Page 26: ...B34 SM3 AMT200B34 IM2 AMiT Fabriqu par Industries Dettson inc 3400 boulevard Industriel Sherbrooke Qu bec Canada J1L 1V8 www dettson ca INSTALLATEUR TECHNICIEN UTILISER LES RENSEIGNEMENTS DANS CE MANU...

Page 27: ...FORMATION 9 FIGURES Figure 1 Ajustement du limiteur et r gulateur de ventilateur combin 7 Figure 2 Mod le AMT1 IM2 12 Figure 3 Mod le AMT1 SM1 12 Figure 4 Mod le AMT2 IM2 13 Figure 5 Mod le AMT2 SM3 1...

Page 28: ...de chauffage Ne jamais laisser de chiffons ou de papier proximit de l unit AVERTISSEMENT RISQUE ENVIRONNEMENTAL Ne pas suivre cet avertissement peut polluer l environnement Retirer et recycler toutes...

Page 29: ...avant de l appareil de chauffage central environ 152 4 mm 6 du plafond et du plancher de l espace ferm Le tableau 1 ci dessous indique les dimensions minimales requises pour les ouvertures de ventila...

Page 30: ...ils de chauffage au combustible solide et ou CSA B139 Code d installation Cet appareil de chauffage central est homologu pour tre utilis avec un vent de type L Inspection pr alable l installation du s...

Page 31: ...MENT L ext rieur de l unit doit poss der une mise la terre ininterrompue pour minimiser les risques de blessures corporelles si jamais un probl me lectrique se produisait Une vis verte de mise la terr...

Page 32: ...d une trousse de test mesurer l indice de fum e et l ajuster une trace de fum e entre 0 et 1 Il est recommand d utiliser la trousse du test de fum e Bacharach ou un quivalent 2 Pour les installations...

Page 33: ...t du ventilateur est contr l par le contr leur m canique bim tallique de ventilation et est ajust en usine pour D part 43 C 110 F et Arr t 32 C 90 F Ces ajustements doivent tre consid r s comme MAXIMU...

Page 34: ...ut de l appareil de chauffage central 5 Nettoyer le tuyau secondaire et le cylindre principal l aide d une brosse rigide et d un aspirateur 6 Avant le r assemblage inspecter l changeur de chaleur et l...

Page 35: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Page 36: ...1 5 5 AFUE partir du standard CSA B212 et des lois canadiennes 84 7 83 9 83 1 SYST ME LECTRIQUE Volts Hertz Phase Tensions de fonctionnement volts Consommation Amps Amp minimum p r grosseur du fil Lon...

Page 37: ...DESSUS LECONDUIT DERACCORDEMENT 22 86 cm 9 DEVANT FOURNAISE 20 32 cm 8 0 6 m 24 DESSUS APPLICATION C T 0 2 C E 0 3 C E 0 4 C E 0 5 C E HIGH 1425 1350 1305 1250 MED HIGH 1130 1045 1000 950 MED LOW 840...

Page 38: ...12 Figure 2 Mod le AMT1 IM2 Figure 3 Mod le AMT1 SM1...

Page 39: ...13 Figure 4 Mod le AMT2 IM2 Figure 5 Mod le AMT2 SM3...

Page 40: ...14 Figure 6 Diagramme lectrique AMT1 IM2 et AMT2 IM2...

Page 41: ...15 Figure 7 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage seulement...

Page 42: ...16 Figure 8 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage et option climatisation...

Page 43: ...17 Figure 9 Liste de pi ces mod le AMT1 IM2 B50054B...

Page 44: ...UR B01716 01 23 PANNEAUM ONTAGEELECTRIQUE B01133 24 PANNEAUELECTRIQUEINTERIEUR B01209 25A ASSPORTED ACCES B01384 25B ISOLATIONPORTED ACCESS B01258 01 25C ISOLATIONCOTEPORTED ACCES B01259 02 25D ISOLAT...

Page 45: ...19 Figure 10 Liste de pi ces mod le AMT1 SM1 B50055B...

Page 46: ...B01723 01 19 A SSPA NNEA UA V A NT B01827 01 20 ISO LA TIO NPA NNEA UA V A NT B01722 21 PLA Q UEDETHERM O DISC B01843 22 A SSPO RTED O BSERV A TIO N B02111 23 CO NDUITDECO IN B01818 24 CO UV ERCLEDEB...

Page 47: ...21 Figure 11 Liste de pi ces mod le AMT2 SM3 B50056B...

Page 48: ...lation B0176 8 01 18 ISO LATIO NPAN NEAUAVANT B0176 7 19 ASSCO N DU ITELECTRIQ U E B0183 0 20 CAC HEFIL B0176 3 21 ASSPLAN CHE R B0176 9 22 A ASSM O TEU R 1 3HPC OM PLET C om prendm oteuretasse m blag...

Page 49: ...23 Figure 12 Liste de pi ces mod le AMT2 IM2 B50057C B50057C...

Page 50: ...et isolation B01384 23B ISOLATION PORTE D ACCESS B01258 01 23C ISOLATION COTE PORTE D ACCES B01259 02 23D ISOLATION COTE PORTE D ACCES B01259 01 24 CONDUIT DE COIN B01220 25 COTE GAUCHE COMPARTIMENT...

Reviews: