2.4) LIMIT
CONTROL
CHECK
The Limit Control is factory adjusted according to Figure 1.. After the
furnace has been in operation for at least 15 minutes, restrict the
return air supply by blocking the filters or closing the return registers
and allow the furnace to shut down on high limit. The burner will shut
OFF and the main blower should continue to run.
Remove the restriction and the burner should come back on in a few
minutes.
For Year Round Air Conditioning
The furnace is designed for use in conjunction with cooling
equipment to provide year round air conditioning. The blower has
been sized for both heating and cooling; however, the fan motor
speed may need to be changed to obtain the necessary cooling
airflow.
Heating
The blower speed is factory set to deliver the required airflow at
normal duct static pressure.
Cooling
The blower speed may be adjusted in the field to deliver the required
airflow for cooling, as outlined in Table 5, according to the selected
model.
Constant Blower Switch
This furnace is equipped with a constant low speed blower option.
Whenever the room thermostat is not calling for heating or cooling,
the blower will run on low speed in order to provide air circulation. If
this constant blower option is not desired, the rocker switch on the
side of the control box can be used to “turn off” this feature.
2.4.1) Fan-Limit adjustment and blower regulator
Modification of the “FAN ON” and “HI” limit settings on the Fan-Limit
can cause malfunctioning of the furnace and result in premature
wear of the heat exchanger.
CAUTION
Modification of the factory set limits will void the
warranty.
Figure 1: Fan-limit adjustment and blower regulator
DNS-0355 Rev A
1
Limit “FAN OFF”
90
°
F
2
Limit “FAN ON”
110
°
F
3
Limit “HI”
Model: AMT1-SM1 & AMT1-IM2
170
°
F
Model: AMT2-IM2
190
°
F
Model: AMT2-SM3
180
°
F
Summary of Contents for AMT100B34-IM2
Page 13: ...13 Figure 2 Model AMT1 IM2 Figure 3 Model AMT1 SM1...
Page 14: ...14 Figure 4 Model AMT2 IM2 Figure 5 Model AMT2 SM3...
Page 15: ...15 Figure 6 Wiring diagram AMT1 IM2 and AMT2 IM2...
Page 16: ...16 Figure 7 Wiring diagram AMT1 SM1 and AMT2 SM3 heating only...
Page 17: ...17 Figure 8 Wiring diagram MT1 SM1 and AMT2 SM3 heating and optional cooling...
Page 18: ...18 Figure 9 Parts list AMT1 IM2 B50054B...
Page 20: ...20 Figure 10 Parts list AMT1 SM1 B50055B...
Page 22: ...22 Figure 11 Parts list AMT2 SM3 B50056B...
Page 24: ...24 Figure 12 Parts list AMT2 IM2 B50057C...
Page 38: ...12 Figure 2 Mod le AMT1 IM2 Figure 3 Mod le AMT1 SM1...
Page 39: ...13 Figure 4 Mod le AMT2 IM2 Figure 5 Mod le AMT2 SM3...
Page 40: ...14 Figure 6 Diagramme lectrique AMT1 IM2 et AMT2 IM2...
Page 41: ...15 Figure 7 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage seulement...
Page 42: ...16 Figure 8 Diagramme lectrique AMT1 SM1 et AMT2 SM3 chauffage et option climatisation...
Page 43: ...17 Figure 9 Liste de pi ces mod le AMT1 IM2 B50054B...
Page 45: ...19 Figure 10 Liste de pi ces mod le AMT1 SM1 B50055B...
Page 47: ...21 Figure 11 Liste de pi ces mod le AMT2 SM3 B50056B...
Page 49: ...23 Figure 12 Liste de pi ces mod le AMT2 IM2 B50057C B50057C...