DS7400Xi-AT (Ver. 3+) Reference Guide Copyright © 1995-2000 Detection Systems, Inc. Page 20
• Battery Restoral: This report is sent when a low battery condition
restores.
• AC Fail: This report is sent when an AC failure condition occurs.
This report may be delayed in address 0197.
• AC Failure Report Delay
The AC power loss report can be programmed to delay for up to
254 minutes (see address 0197). (The same delay would also
apply to the AC restoral report.)
- If another report is sent during this delay period, the AC fail
report will be sent along with this report.
- If the AC power restores during this delay period, the AC loss
report will not be sent.
- Programming address 0197 as FF causes the report to be sent
at a random interval of at least 15 minutes, but no more than 2
hours after the AC failure occurs.
• AC Restoral: This report is sent when an AC failure condition
restores.
• Communicator Test/System Normal: This report is sent at the
24-hour check-in time if there is not a control trouble, an active
fire alarm that has not been acknowledged, a fire trouble, or a
supervisory condition. Note: To send a Communicator Test even
if one of these conditions exists, program the Communicator
Test/System Off Normal.
• Remote Program Successful: This report is sent after a Remote
Program session if the session was terminated properly.
• Remote Program Unsuccessful: This report is sent after a
Remote Program session if some error has occurred or the
session did not terminate properly.
• Local Program Successful: This report is sent when local
programmer’s mode is exited and there is no error associated
with the programming.
• Local Program Unsuccessful: This report is sent when local
programmer’s mode is exited and there has been some error
associated with the programming.
• System Trouble: This report is sent when a control trouble
condition occurs. System Trouble must be programmed to send
RF (wireless) trouble reports.
• System Trouble Restoral: This report is sent when all system
trouble conditions restore.
• Communicator Test/System Off Normal: This report is sent at
the 24-hour check-in time if there is a control trouble, an active
fire alarm that has not been acknowledged, a fire trouble, or a
supervisory condition.
• Exit Error: This report is sent if an exit error occurs. An exit error
occurs when an entry/exit zone is still violated at the end of the
exit delay. If this happens, the entry delay will begin. If the system
is not disarmed before the entry delay expires, an alarm report
for the effected zone will be sent and the Exit Error report will be
sent. If this report is not programmed, the control will not sound
the exit error warning.
• Recent Closing: This report is sent, along with any alarm reports,
when there is an alarm within the first five minutes after the system
has been armed.
• System Walk Test: This report is sent when a system test has
been started ([#] [8] [1] key sequence). Zone reports are sent
during a system test.
• System Walk Test Restoral: This report is sent when the system
test has been completed or has timed-out.
• Fire Walk Test: This report is sent when a Fire Walk Test has been
started ([#] [9] [1] key sequence). Zone reports are not sent during
a Fire Walk Test.
• Fire Walk Test Restoral: This report is sent when the Fire Walk
Test has been completed or has timed-out.
• Mux. Smoke Low Temperature Report: This supervisory report
is sent when a MX280 Series smoke detector with a low
temperature feature detects a temperature of 45°F (7.5°C) or
less for a period of 10 minutes or more.
• Mux. Smoke Low Temperature Restoral: This report is sent
when a MX280 Series smoke detector with a low temperature
alarm determines that the temperature has risen above 45°F
(7.5°C).
• Dirty Chamber Report: This report is sent when a MX280 Series
smoke detector fails to pass the “Chamber Check” sensitivity
test.
• Dirty Chamber Restoral: This report is sent when a MX280
Series smoke detector has been returned to normal operation
after service.
6.14
Phone Number General Control
Programming
• Enable Remote Programmer Callback: If programmed, when
the remote programmer tries to initiate a session with the panel,
the panel will hang up and call the remote programmer phone
number.
- This ensures the correct remote programmer is initiating the
call.
• Dial Pulse on all Phone Numbers: If programmed, the panel will
dial phone number 1, 2, and the remote programmer phone
number 3 using the pulse format.
• Dial Tone on all Phone Numbers: If programmed, the panel will
dial phone number 1, 2, and the remote programmer phone
number 3 using the tone format.
6.15
Phone Answering Programming
• Answering Machine Bypass: This feature allows the panel to
answer incoming calls when answering machines are used. If
the line rings, stops ringing, then rings again within one minute,
the panel will seize the phone line on the first ring.
• Phone Answering Programming: The panel can be
programmed to answer the phone after a selected number of
rings for remote programming access. It can also be programmed
to answer the phone after a different number of rings when in
armed or disarmed states.
- This can be used to call the panel location and determine its
arming state.
6.16
FCC Compliance Notice
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment
generates, uses and can radiate radio frequency energy and if not
installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is
no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to
radio or television reception, which can be determined by turning
the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
Summary of Contents for DS7400Xi-AT