DS7400Xi-AT (Ver. 3+) Reference Guide Copyright © 1995-2000 Detection Systems, Inc. Page 49
11.21 Timer Programming: Program Addresses (0191-0193, 0195-0196)
11.22 AC Fail Report Delay Programming: Program Address (0197)
The AC Fail Delay Times are programmed as Hexadecimal values. For
example:
00 = Send only with next report
1 *4 = 30 minute delay
3 *2 = 60 minute delay
78 = 120 minute delay
*5 0 = 240 minute delay
*5 *5 = Random delay (at least 15 minutes, but less than 120 minutes)
(*0 - *5 are Hex values. They will display as A through F at the keypads.)
See Glossary (section 6.13) for further details.
If the DS7400Xi-AT Version 3+ is configured as a
Commercial Fire Mode System (Address 0186 - section 1-
*2) the AC Failure Report is sent on a random basis at any
time between 6 and 12 hours after the failure of the AC
Primary power when any other report is sent to the Central
Station. This delay is to comply with NFPA-72-1996 Section
1-5.8.6.3 which requires that the battery achieve a discharge
of between 25% and 50% before the AC Failure Report is
sent. The delay time set into Address 0197 has no affect
when the DS7400Xi-AT is in the Commercial Fire Mode.